8
Installation and Servicing
SECTION 1 - GENERAL
15 18 26 32
Gas supply
2H - G20 - 20mbar
Gas Supply Connection
22mm copper compression
Injector Size
m
3.40
3.35
4.30
4.80
Flow Connection
Central Heating
22mm copper compression
Return Connection
Central Heating
22mm copper compression
Flue Terminal Diameter
mm
100
Average Flue Temp-Mass Flow Rate (CH)
ºC (g/s) 72ºC (6 g/s) 67ºC (8 g/s)
70ºC (11 g/s) 70º (14 g/s)
CO
2
Content (± 0.7)
Max. CH
9.4 %
9.5 %
9.5 %
9.5 %
Min CH
8.3 %
8.5 %
8.4 %
8.2 %
Maximum Working Pressure (Sealed Systems)
bar
2.5
Electrical Supply
230 V ~ 50 Hz.
Power Consumption
W
73
88
98
102
Fuse Rating
External : 3A Internal
: 4A Time Delay
Water content
Central Heating
litre
1.1
1.5
1.8
2.2
Packaged
Weight
kg
38.0 38.8 40.2 42.2
Maximum Installation Weight
kg
30.7
31.5
32.9
34.3
Boiler Casing Size
Height
mm
740
Width mm
445
Depth mm
330
Heat Exchanger Weight without Burner
kg
6.0
7.3
8.2
9.5
Table 1 - General Data
Note.
Gas consumption is calculated using a
calorific value of 38.7 MJ/m
3
gross or 34.9 MJ/m
3
nett
To obtain the gas consumption at a different
calorific value:
a.
For l/s
- divide the gross heat input (kW) by
the gross C.V. of the gas (MJ/m
3
)
b.
For ft
3
/h
- divide the gross heat input (Btu/h)
by the gross C.V. of the gas (Btu/ft
3
)
c.
For m
3
/h
- multiply l/s by 3.6
Key to symbols
GB
= United Kingdom
IE
= Ireland
(Countries of destination)
PMS
= Maximum operating pressure of water
C
13
C
33
C
53
* = A room sealed appliance designed for connection via ducts to a
horizontal or vertical terminal, which admits fresh air to the burner
and discharges the products of combustion to the outside through
orifices which, in this case, are concentric. The fan is up stream of
the combustion chamber. (*Note.
C
53
covers optional high level and
balconly flue kits only.)
I
2H
= An appliance designed for use on 2nd Family gas, Group H only.
* The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by a notified body.
Boiler Input :
Max.
Min.
15 18 26 32 15 18 26 32
Boiler Input ‘Q’
Nett CV
kW
15.1
18.1
26.1
32.1
3.0
3.6
5.2
6.4
Gross CV
kW
16.8
20.1
29.0
35.6
3.3
4.0
5.8
7.1
Gas Consumption
m
3
/h 1.559 1.869 2.695 3.314 0.310 0.372 0.537 0.661
Boiler Output :
Non Condensing
kW
15.0
18.0
26.0
32.0
3.0
3.6
5.2
6.4
70
o
C Mean Water temp.
Condensing
kW 16.2
19.3
27.9
34.3
3.2
3.9
5.6
6.8
40
o
C Mean Water temp.
Seasonal efficiency* SEDBUK 2005
91
91.1
91.1
91.1
n/a
Seasonal efficiency* SEDBUK 2009 88.9
89.3
89.3
89.3
n/a
NOx Classification
Class 6
Table 2 - Performance Data - Central Heating
CO
2
Content (± 0.7)
Max. DHW
9.6
9.8
9.4
Min. DHW
8.1
8.5
8.0
Summary of Contents for VOGUE MAX SYSTEM 15
Page 4: ...4 Installation and Servicing...
Page 6: ...6 Installation and Servicing...
Page 68: ...68 SHORT LIST OF PARTS Installation and Servicing...
Page 74: ...74 Installation and Servicing NOTES...
Page 75: ...75 Installation and Servicing NOTES...
Page 76: ...76 Installation and Servicing NOTES...
Page 77: ...77 Installation and Servicing NOTES...
Page 78: ...78 Installation and Servicing NOTES...