3
OPEN VENT SYSTEM
REQUIREMENTS
4
SCHEMATIC PIPEWORK AND SYSTEM BALANCING
The boiler does not normally need a
bypass but at least some radiators on the
heating circuit, of load at least 60% of the
boiler output, must be provided with twin
lockshield valves so that this minimum
heating load is always available (see
footnote re. thermostatic radiator valves).
Balancing
1.
Set the programmer to ON for both CH
and HW. Turn the cylinder thermostat
down. Close the manual or
thermostatic valves on all radiators,
leaving the twin lockshield valves (on
the radiators referred to above) in the
open position. Turn up the room
thermostat and adjust these
lockshield valves to give boiler flow
and return temperatures not more
than 15°C apart. These valves should
now be left as set.
Return & flow
connections
SE 30 - 60 = 22 mm
SE 70 - 80 = 28 mm
Thermostatic Radiator Valves
Caradon Plumbing Ltd
. support the recommendations made in
BS. 5449, and by leading manufacturers of domestic heating
controls, that heating systems utilising the thermostatic radiator
valve control of temperature in individual rooms shall also be fitted
with a room thermostat, controlling the temperature in a space
served by radiators not fitted with such a valve.
Such an arrangement will provide for potentially more efficient
control of the environment and will also avoid the continuous
running of the circulation pump during programmed heating ON
periods - thus saving electrical energy.
It is, therefore, strongly recommended that, when thermostatic
radiator valves are used, space heating temperature control over a
living/dining area or a hallway having a heating requirement of at
least 60% of the boiler heat output, is achieved using a room
thermostat whilst other rooms are individually controlled by
thermostatic radiator valves.
2.
Open all manual or thermostatic radiator
valves and adjust the lockshield valves on
remaining radiators to give around 11°C
temperature drop at each radiator.
3.
Turn up the cylinder thermostat and adjust
the cylinder balancing valve so that the
cylinder achieves a maximum flow consistent
with adequate flow to the radiators. Check
that with only the domestic hot water loop in
circuit a differential temperature of 15 °C
across the boiler is not exceeded.
4.
Adjust room and cylinder thermostats and
programmer to NORMAL settings.
The system should be vented directly off the boiler flow pipe, as
close to the boiler as possible. The cold feed entry should be
inverted and MUST be positioned between the pump and the
vent, and not more than 150mm (6") away from the vent
connection.
Note.
Combined feed and vent pipes may also be fitted.
There should be a minimum height, 450mm (18"), of open vent
above the cistern water level. If this is not possible refer to
Frame 5
.
The vertical distance between the highest point of the system and the
feed/expansion cistern water level MUST not be less than 450 mm (18"). The
pump must be fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing a maximum
11°C (20°F) temperature differential across the boiler with the whole of the
heating circuit open (e.g. Grundfos UPS 15/50, 15/60 or equivalent). With the
minimum flow circuit allowed by the controls the differential must not exceed
15 °C.
The vertical distance between the pump and feed/expansion cistern MUST
comply with the pump manufacturer's minimum requirements, to avoid
cavitation. Should these conditions not apply either lower the pump position or
raise the cistern above the minimum requirement specified by
Caradon
Plumbing Ltd.
The isolation valves should be fitted as close to the pump as
possible.