25
INSTALLATION
icos system -
Installation and Servicing
29 WATER CONNECTIONS
Notes.
1.
For heating loads in excess of 60,000 Btu/h use 28mm x 22mm
connectors to connect the boiler flow and return pipes to 28mm
system pipework.
2.
Do not subject any of the isolating valves to heat as the seals
may be damaged.
nm84
6
1
22mm copper pipe
Isolating valve
(
shown in the
open position
)
Piping frame
Drain
point
Condensate drain
pipe located here
22mm copper pipe
Isolating valve
(
shown in the
open position
)
Pressure gauge
FLOW
RETURN
Compression
gas coc
k
The safety valve is located at the bottom RHS of the boiler.
The discharge pipe should be positioned so that the discharge of water or steam cannot create a hazard to the
occupants of the premises or damage the electrical components and wiring.
28 SAFETY VALVE DRAIN
INST
ALLA
TION
200214-11.pmd
17/11/2006, 09:35
25