21
Buccaneer GTE -
Installation & Servicing
INSTALLATION
34 CONNECTIONS OF COMPONENTS (NOT SUPPLIED)
WARNING.
Sensor cables must be separated from cables in 230V circuits (see Frame 32).
Additional system components may be wired as follows:
-
Room thermostat at terminals 17 and 18 after removal of link (zone A).
-
Room thermostat at terminals 19 and 20 zone B (do not fit link if zone B not used).
-
Safety contact to terminals 4 and 5 after removing link.
-
Remote alarm to indicate overheat, low water pressure etc. to terminals 6 and 7.
If only one circuit is used, connect the room thermostat to circuit A
and DO NOT fit link connector TAM B.
Removeable
link
Removeable
link
Safety
contact
Alarm
light
Room
thermostat
(Zone A)
Room
thermostat
(Zone B)
buc7942
INST
ALLA
TION