170
the gas (large) pipe;
When the vertical pipe height difference is more than 5 meters, then for every 5 meters an oil loop must be
installed at the bottom of the gas (large) pipe, and a short loop (liquid ring) should be installed at the exit of the
indoor unit liquid (small) pipe;
When the connecting gas pipe vertical height difference is less than 5 meters but the constant rise distance is
too long, an oil loop should be installed in the gas (large) pipe every 10 meters.
◇
When the outdoor and indoor units are at the same elevation, the oil deposit bend and liquid ring do not need
to be installed, if the horizontal connecting pipe length is less than 10 meters.
When the horizontal connecting pipe length is more than 10 metres, install an oil loop in the gas (large) pipe
every 10 metres.
Note:
This chart is for explanation purposes. An actual installation will differ from this according to the site conditions.
When making an oil trap the radius of the bend should be between 1.5 and 2 times the pipe diameter.
7.3. Electrical connection
7.3.1Electrical connection precaution
Warning
Installation of electric items must be carried out by qualified, professional technicians. An isolated circuitry
should be fixed with whole-pole disconnection devices, which is with at least 3mm gap of touch point. .
Power supply and indoor to outdoor connection should use special cable. Providing the necessity of
installation or replacement, the professional technician of service store appointed by manufacturer must
be required, while self-operation by users is prohibited.
In case of any electric shock accident, the creepage protection devices /power supply on-off and breaker
must be required with power supply.
The specification of fuse for single phase control board is F5AL 250V, while for 3 phase control board,
both indoor and outdoor unit, it is F3.15AL 250V
。
Machine must be earthed surely. If not, it’ll be probably caused creepage.
Equivalent 227IEC53(RVV) type of power cord of GB5023 or the excelled must be required. The cords
should be fixed properly against broken, while ends/joints of cords is under outside force. Improper
connection or fixation will cause disaster like fire….etc. Equivalent 245IEC57(YZW) type of power cord of
GB5023 or the excelled must be used as connection line of indoor and outdoor.
Summary of Contents for ICC(ICA)-**HR-SA6-NI
Page 1: ......
Page 3: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ...21 ...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ...50 ...
Page 51: ...54 ...
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 67: ...540 760 111 539 257 287 322 130 300 326 590 800 540 4 10 19 370 ...
Page 68: ...130 370 4 10 19 540 800 690 326 300 606 332 400 354 11 71 903 857 ...
Page 69: ...148 1255 180 945 413 373 4 10 19 585 340 ...
Page 72: ...152 ...
Page 73: ......
Page 74: ......
Page 104: ...186 7 Failure analysis Wired controller communication failure ...
Page 105: ...187 Communication failure between indoor and outdoor unit ...
Page 106: ...188 Outdoor protection phase sequence ...
Page 107: ...189 Cooling high pressure protection ...
Page 108: ...190 Heating high pressure protection ...
Page 109: ...191 Cooling low pressure protection ...
Page 110: ...192 Heating low pressure protection ...
Page 111: ...193 Cooling exhaust temperature protection ...
Page 112: ...194 Heating exhaust temperature protection ...
Page 113: ...195 Refrigerant shortage or four way valve failure protection ...
Page 114: ...196 Sensor failure protection ...
Page 115: ...197 No action after power on ...
Page 116: ...198 Poor effect ...
Page 117: ...199 ...
Page 118: ...200 Abnormal sound or viberation ...
Page 119: ...201 ...
Page 120: ...202 Abnormal odor ...
Page 121: ...203 Air switch action when air conditioner starting up ...
Page 122: ...204 Air conditioner water leakage ...