169
Additional refrigerant charge
When pipe length exceeds 5m, please add refrigerant according to the table below:
Connection
piping
Piping size)
Additional refrigerant
charge amount (kg/m)
Gas pipe
Liquid pipe
Piping
between
indoor and
outdoor unit
φ9.52×0.75mm
φ6.35×0.75mm
0.02
φ12.7×1mm
φ6.35×0.75mm
0.02
φ15.88×1mm
φ9.52×0.75mm
0.05
φ19.05×1mm
φ9.52×0.75mm
0.07
φ19.05×1mm
φ12.7×1mm
0.09
Others
Users to install the air conditioner at site shall ensure that the oil can return to the unit smoothly.
◇
Horizontal pipes should incline toward the outdoor unit using a 20:1 slop.e
◇
If there is a height difference between the indoor and outdoor unit, oil loops should be installed in the inter
connecting gas (large) pipe;
When the vertical pipe height difference is less than 5 meters, an oil loop should be installed at the bottom of
Summary of Contents for ICC(ICA)-**HR-SA6-NI
Page 1: ......
Page 3: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ...21 ...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ...50 ...
Page 51: ...54 ...
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 67: ...540 760 111 539 257 287 322 130 300 326 590 800 540 4 10 19 370 ...
Page 68: ...130 370 4 10 19 540 800 690 326 300 606 332 400 354 11 71 903 857 ...
Page 69: ...148 1255 180 945 413 373 4 10 19 585 340 ...
Page 72: ...152 ...
Page 73: ......
Page 74: ......
Page 104: ...186 7 Failure analysis Wired controller communication failure ...
Page 105: ...187 Communication failure between indoor and outdoor unit ...
Page 106: ...188 Outdoor protection phase sequence ...
Page 107: ...189 Cooling high pressure protection ...
Page 108: ...190 Heating high pressure protection ...
Page 109: ...191 Cooling low pressure protection ...
Page 110: ...192 Heating low pressure protection ...
Page 111: ...193 Cooling exhaust temperature protection ...
Page 112: ...194 Heating exhaust temperature protection ...
Page 113: ...195 Refrigerant shortage or four way valve failure protection ...
Page 114: ...196 Sensor failure protection ...
Page 115: ...197 No action after power on ...
Page 116: ...198 Poor effect ...
Page 117: ...199 ...
Page 118: ...200 Abnormal sound or viberation ...
Page 119: ...201 ...
Page 120: ...202 Abnormal odor ...
Page 121: ...203 Air switch action when air conditioner starting up ...
Page 122: ...204 Air conditioner water leakage ...