57
water leakage, air leakage etc. will be resulted;
◇
Tighten the nuts and ensure that the hooks are tightly connected to the nuts and sMDms
, and there is no
phenomenon of virtual hanging;
◇
After the unit is installed ensure it is secure and does not shake or sway.
6.4 Drainage pipe installation
◇
The drain pipe should be properly insulated to prevent the generation of condensation
, see picture as
follows:
Heat insulation material: rubber insulation pipe with the thickness of more than 8mm
◇
Drainage pipe must have a downward gradient (1 / 50 1 / 100).If the drain pipe is installed ups and
downs, it will cause water backflow or leakage etc.
The pipe should not rise at any point.
◇
When finish installation,please carry out the drainage test to ensure that the water flow through the
pipeline fluently, and carefully observe the junction to ensure that there is no water leakage at the
junction. If the unit is installed in the newly built house, strongly recommend that this test taken before
the ceiling installation. Even it is the heating only unit, this test is unavoidable.
Summary of Contents for ICC(ICA)-**HR-SA6-NI
Page 1: ......
Page 3: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ...21 ...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ...50 ...
Page 51: ...54 ...
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 67: ...540 760 111 539 257 287 322 130 300 326 590 800 540 4 10 19 370 ...
Page 68: ...130 370 4 10 19 540 800 690 326 300 606 332 400 354 11 71 903 857 ...
Page 69: ...148 1255 180 945 413 373 4 10 19 585 340 ...
Page 72: ...152 ...
Page 73: ......
Page 74: ......
Page 104: ...186 7 Failure analysis Wired controller communication failure ...
Page 105: ...187 Communication failure between indoor and outdoor unit ...
Page 106: ...188 Outdoor protection phase sequence ...
Page 107: ...189 Cooling high pressure protection ...
Page 108: ...190 Heating high pressure protection ...
Page 109: ...191 Cooling low pressure protection ...
Page 110: ...192 Heating low pressure protection ...
Page 111: ...193 Cooling exhaust temperature protection ...
Page 112: ...194 Heating exhaust temperature protection ...
Page 113: ...195 Refrigerant shortage or four way valve failure protection ...
Page 114: ...196 Sensor failure protection ...
Page 115: ...197 No action after power on ...
Page 116: ...198 Poor effect ...
Page 117: ...199 ...
Page 118: ...200 Abnormal sound or viberation ...
Page 119: ...201 ...
Page 120: ...202 Abnormal odor ...
Page 121: ...203 Air switch action when air conditioner starting up ...
Page 122: ...204 Air conditioner water leakage ...