background image

6

4)  Once the current has stabilized, a reading should be 

taken and the anticipator adjusted to that value.  If 
longer heating cycles are desired, the anticipator can 
be set to a higher value 

2.5.2.

Ducts and filters 

The ducts must be sized such a way as to accommodate the 
specified airflow and the available static pressure.  Refer to the 
applicable local and/or national installation codes. 

Insulate the ducts that lead through non-heated areas.  Use 
flexible supply and return air connectors to avoid the 
transmission of vibration.  To make the unit run even quieter, 
the installer should: 

1)  Use two elbows between each outlet and the supply 

and return air plenum; 

2)  Cover the vertical sections of the supply and return air 

duct with soundproofing material; 

3)  Use baffles in short radius elbows; 
4)  Use flexible hangers to suspend the ducts. 

The 

SUPREME

 furnace is equipped with a filter frame for the 

blower compartment.  It must be installed on the outside of one 
of the three sides or the bottom of the furnace.  Once the 
location of the installation has been determined, use the four 
square knockouts for ease of cutting the opening. 

A heat pump or an air conditioner can be added to this furnace, 
in either the supply or return air duct.  Carefully follow the 
instructions provided with these appliances to ensure proper 
installation and hook-up to the electric furnace.  Refrigerant and 
drainage pipes must in no way hinder access to the furnace 
panels. 

2.6 

SUPPLY AIR ADJUSTMENTS

On  units  equipped  with  4-speed  blower  motors,  the  supply  air 
must  be  adjusted  based  on  heating/air  conditioning  output  and 
the static pressure of the duct system.  For the desired airflow, 
refer to the following table as well as the airflow tables based on 
static  pressure  in  the  Technical  Specifications  section  of  this 
manual. 

For the adjustment of the airflow on heating mode, to obtain the 
temperature rise described in the technical specification table on 
p.10,    the  orange  wire  must  be  positioned  on  the  terminal 
corresponding  to  the  LOW,  MED-LOW,  MED-HIGH  or  HIGH 
blower speed.  Blower speed are adjusted in factory for 0.5 inch 
static pressure. 

Supply air adjustment on heating mode 

FURNACE

INPUT 

POWER 

KW 

HP MOTOR 

STATIC

PRESSURE

(in. w.c) 

RECOMMENDED
BLOWER SPEED 

0.2

LOW 

FEM10

10

1/3

0.5

LOW 

0.2

MED-LOW 

FEM15

15

1/3

0.5

MED-LOW 

0.2

MED-LOW 

FEM18

18

1/3

0.5

MED-LOW 

0.2

MED-LOW 

FEM20

20

1/3

0.5

MED-HIGH

0.2

MED-HIGH

FEM23

23

1/3

0.5

MED-HIGH

0.2

MED-LOW 

FEM20

20

1.0

0.5

MED-LOW 

0.2

MED-LOW 

FEM23

23

1.0

0.5

MED-LOW 

0.2

MED-LOW 

FEM27

27

1.0

0.5

MED-LOW 

For the adjustment of the airflow on air-cooling mode, to obtain 
a sufficient airflow (350 to 450 CFM per ton), the blue wire must 
be positioned on the terminal corresponding to the LOW, MED-
LOW,  MED-HIGH  or  HIGH  blower  speed.    Blower  speeds  are 
adjusted in factory for 0.5 inch static pressure. 

Supply air adjustment on air cooling mode 

FURNACE

HP MOTOR 

COOLING 

CAPACITY  

(0.5” w.c.) 

RECOMMENDED
BLOWER SPEED 

1.5

LOW 

2.0

MED-LOW 

2.5

MED-HIGH

FEM10, 15, 18, 

20 and 23 

1/3

3.0

HIGH

2.5

LOW 

3.0

MED-LOW 

3.5

MED-HIGH

4.0

HIGH

FEM20, 23 and 

27

1.0

5.0

HIGH

If  the  heating  and  air-cooling  speed  are  the  same,  the  orange 
wire  and the blue  wire can be connected  on the same terminal 
on the motor. 

2.7 

INSTALLATION OF ACCESSORIES

WARNING

Electrical shock hazard. 

Turn  OFF  electrical  power at  the  fuse  box  or  service  panel 
before  making  any  electrical  connections  and  ensure  a 
proper  ground  connection  is  made  before  connecting  line 
voltage. 

Failure to do so can result in death or bodily injury.

Summary of Contents for SUPREME FEM10-M2401AM-A

Page 1: ...ebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper DNS 0981 Rev A MULTI POSITION INSTALLER SERV...

Page 2: ...ON 8 5 INFORMATION 9 TABLES AND FIGURES FIGURE 1 CONFIGURATION UPFLOW INSTALLATION 4 FIGURE 2 CONFIGURATION DOWNFLOW INSTALLATION 4 FIGURE 3 CONFIGURATION HORIZONTAL INSTALLATION 4 FIGURE 4 MANUAL FUR...

Page 3: ...ualified persons can result in hazards to them and to others Installations must conform to local codes or in the absence of same to codes of the country having jurisdiction The information contained i...

Page 4: ...uding 20 k W can be installed with a zero clearance to combustible material Ducts for furnaces of 23 kW or more must have a clearance of 25 mm 1 to combustible material for the first 0 9 m 36 of duct...

Page 5: ...ontrol the temperature of the area to be heated Follow the instructions supplied with the thermostat Install the thermostat on an interior wall in a location where it will not be subject to direct sun...

Page 6: ...airflow refer to the following table as well as the airflow tables based on static pressure in the Technical Specifications section of this manual For the adjustment of the airflow on heating mode to...

Page 7: ...t of the room is in the heating mode and is set higher than the ambient temperature To start the unit turn the main electrical switch on 3 2 OPERATING SEQUENCE Heating mode 1 The thermostat closes the...

Page 8: ...pply air plenum just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 1 AIR FILTER The filter supplied with the unit is t...

Page 9: ...ame and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total pres...

Page 10: ...84 100 112 125 119 134 155 Maximum size circuit breaker Amp 2 60 90 100 125 125 125 150 175 BLOWER DATA factory adjusted to a static pressure of 0 5 W C Blower speed at 0 50 W C static pressure LOW M...

Page 11: ...5 CFM more or less These readings were taken with the air filter installed TABLE 3 Air Flow CFM SUPREME with 1 HP motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7 LOW 1035 1030 1030 1025 1020 1020 1015 MED LOW 1315...

Page 12: ...12 FIGURE 6 Wiring Diagram 10 kW with 1 3 HP motor...

Page 13: ...13 FIGURE 7 Wiring Diagram 15 kW with 1 3 HP motor...

Page 14: ...14 FIGURE 8 Wiring Diagram 18 and 20 kW with 1 3 HP motor and 20 kW with 1 0 HP...

Page 15: ...15 FIGURE 9 Wiring Diagram 23 kW with 1 3 HP and 1 HP motor...

Page 16: ...16 FIGURE 10 Wiring Diagram 27 kW with 1 HP motor...

Page 17: ...COMPONENTS AND REMPLACEMENT PARTS 17...

Page 18: ...18 PARTS LIST Exploded View B50002F Please refer to Table 4 p 20...

Page 19: ...HP 12 B03288 MOUNTING PLATE FOR ELECTRICAL TOP 13 B03289 MOUNTING PLATE FOR ELECTRICAL SIDE 14 L05F004 TERMINAL STRIP 4 POSITION 15 L01H009 RELAY SPDT 24 VAC 16 L01F009 TRANSFORMER 120 24Volts 17 L99...

Page 20: ...7 305891 R02N016 305891 R02N016 305136 R02N017 305136 R02N017 18C 3 305136 R02N017 305891 R02N016 305891 R02N016 305891 R02N016 18D 4 305891 R02N016 305136 R02N017 18E 5 305891 R02N016 Item TABLE 4 FE...

Reviews: