background image

4

2.1 

POSITIONING THE FURNACE

WARNING

Fire and explosion hazard. 

The  furnace  must  be  installed  in  a  level  position,  never 
where it will slope toward the front. 

Do  not  store  or  use  gasoline  or  any  other  flammable 
substances near the furnace 

Non-observance  of  these  instructions  will  potentially  result 
in death, bodily injury and/or property damage. 

CAUTION

This  furnace  is  not  watertight  and  is  not  designed  for 
outdoor installation.  It must be installed in such a manner 
as  to  protect  its  electrical  components  from  water.  
Outdoor  installation  will  lead  to  a  hazardous  electrical 
condition and to premature failure of the equipment 

If  the  furnace  is  installed  in  a  basement  or  on  a  dirt  floor,  in  a 
crawl space for example, it is recommended to install the unit on 
a cement base 2.5 cm to 5.0 cm (1’’ to 2’’) thick. 

The  unit  must  be  installed  in  an  area  where  the  ambient  and 
return air temperatures are above 15˚C (60˚F).  In addition, the 
heater  should  also  be  located  close  to  the  center  of  the  air 
distribution system. 

2.2 

CLEARANCES 

TO 

COMBUSTIBLE 

MATERIAL

2.2.1. 

Heating unit

The  furnace  is  approved  for  zero  clearance  to  combustible 
material regardless of the heating capacity. 

2.2.2. 

Supply air ducts

Ducts  for  furnaces  with  a  heating  capacity  up  to  and  including 
20  k W,  can  be  installed  with  a  zero  clearance  to  combustible 
material.

Ducts for furnaces of 23 kW or more must have a clearance of 
25  mm  (1’’)  to  combustible  material  for  the  first  0.9  m  (36’’)  of 
duct.  Thereafter the clearance can be zero. 

Units  of  23  kW  and  up,  installed  in  the  downflow  position  must 
use  a  DFB-FEM  downflow  base,  which  is  especially  designed 
for  this  purpose.    It  ensures  that  the  required  clearances  are 
being adhered to. 

2.3 

CONFIGURATIONS

2.3.1. 

Upflow installation

The  return  air  opening  may  be  located  on  either  side  of  the 
furnace.  Care should be taken not to damage the wires inside, 
while cutting the opening.  Install the filter rack supplied with the 
unit  according  to  the  instructions  provided  with  it.    It  is  also 
recommended  to  install  the  blower  door  before  handling  or 
moving the unit.  Refer to Figure 1 for additional details. 

Figure 1 

2.3.2. 

Downflow installation

When  the  furnace  is  installed  in  the  downflow  position  on  a 
combustible  floor,  the  clearances  from  combustibles  must  be 
adhered  to.    The  downflow  base  DFB-FEM  can  be  used  to 
ensure these clearances.  Refer to Figure 2 and the installation 
instructions provided with the base. 

Figure 2 

2.3.3. 

Horizontal installation

When  the  furnace  is  installed  in  the  horizontal  position,  either 
suspended or on a combustible floor with a choice of right or left 
discharge,  the  clearances  from  combustible  material  must  be 
adhered to.  Refer to Figure 3 for additional details. 

Figure 3 

Summary of Contents for SUPREME FEM10-M2401AM-A

Page 1: ...ebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper DNS 0981 Rev A MULTI POSITION INSTALLER SERV...

Page 2: ...ON 8 5 INFORMATION 9 TABLES AND FIGURES FIGURE 1 CONFIGURATION UPFLOW INSTALLATION 4 FIGURE 2 CONFIGURATION DOWNFLOW INSTALLATION 4 FIGURE 3 CONFIGURATION HORIZONTAL INSTALLATION 4 FIGURE 4 MANUAL FUR...

Page 3: ...ualified persons can result in hazards to them and to others Installations must conform to local codes or in the absence of same to codes of the country having jurisdiction The information contained i...

Page 4: ...uding 20 k W can be installed with a zero clearance to combustible material Ducts for furnaces of 23 kW or more must have a clearance of 25 mm 1 to combustible material for the first 0 9 m 36 of duct...

Page 5: ...ontrol the temperature of the area to be heated Follow the instructions supplied with the thermostat Install the thermostat on an interior wall in a location where it will not be subject to direct sun...

Page 6: ...airflow refer to the following table as well as the airflow tables based on static pressure in the Technical Specifications section of this manual For the adjustment of the airflow on heating mode to...

Page 7: ...t of the room is in the heating mode and is set higher than the ambient temperature To start the unit turn the main electrical switch on 3 2 OPERATING SEQUENCE Heating mode 1 The thermostat closes the...

Page 8: ...pply air plenum just outside the range of radiant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 1 AIR FILTER The filter supplied with the unit is t...

Page 9: ...ame and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total pres...

Page 10: ...84 100 112 125 119 134 155 Maximum size circuit breaker Amp 2 60 90 100 125 125 125 150 175 BLOWER DATA factory adjusted to a static pressure of 0 5 W C Blower speed at 0 50 W C static pressure LOW M...

Page 11: ...5 CFM more or less These readings were taken with the air filter installed TABLE 3 Air Flow CFM SUPREME with 1 HP motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7 LOW 1035 1030 1030 1025 1020 1020 1015 MED LOW 1315...

Page 12: ...12 FIGURE 6 Wiring Diagram 10 kW with 1 3 HP motor...

Page 13: ...13 FIGURE 7 Wiring Diagram 15 kW with 1 3 HP motor...

Page 14: ...14 FIGURE 8 Wiring Diagram 18 and 20 kW with 1 3 HP motor and 20 kW with 1 0 HP...

Page 15: ...15 FIGURE 9 Wiring Diagram 23 kW with 1 3 HP and 1 HP motor...

Page 16: ...16 FIGURE 10 Wiring Diagram 27 kW with 1 HP motor...

Page 17: ...COMPONENTS AND REMPLACEMENT PARTS 17...

Page 18: ...18 PARTS LIST Exploded View B50002F Please refer to Table 4 p 20...

Page 19: ...HP 12 B03288 MOUNTING PLATE FOR ELECTRICAL TOP 13 B03289 MOUNTING PLATE FOR ELECTRICAL SIDE 14 L05F004 TERMINAL STRIP 4 POSITION 15 L01H009 RELAY SPDT 24 VAC 16 L01F009 TRANSFORMER 120 24Volts 17 L99...

Page 20: ...7 305891 R02N016 305891 R02N016 305136 R02N017 305136 R02N017 18C 3 305136 R02N017 305891 R02N016 305891 R02N016 305891 R02N016 18D 4 305891 R02N016 305136 R02N017 18E 5 305891 R02N016 Item TABLE 4 FE...

Reviews: