Tips & Warnings
Note:
The “T/C ?-type”, with the wire opening detection feature, cannot be
selected when the channel is not being used. As shown in the picture below,
if the field (background is yellow) of the “Channel Enable/Disable Setting”
part shows “+9999.900”, it means that the “Input Range” settings are wrong,
or the channel is set as a “T/C ?-type”, but is not being used.
Note that every channel must be checked.
M-7018Z:
The settings are similar to those of the I-7018Z, but the “Protocol” option should be set to
“Modbus RTU”.
Note: If the RS-485 Port of the TouchPAD uses the Modbus RTU protocol to connect
to the M-7018Z, then the M-7018Z must be set to "Engineering" mode