Relay Output Module
Module Name
tM-P3R3
tM-R5
Relay Output
Output Channels
3
5
Type
Power Relay, Form A (SPST N.O.) Power Relay, Form A (SPST N.O.)
Operating Voltage Range
250 VAC or 30 VDC
250 VAC or 30 VDC
Max. Load Current
5 A
5 A
Operate Time
6 ms
6 ms
Release Time
3 ms
3 ms
5 A @250 VAC 30,000 ops (10
ops/minute) at 75°C
5 A @250 VAC 30,000 ops (10
ops/minute) at 75°C
VDE
5 A @30 VDC 70,000 ops (10
ops/minute) at 75°C
5 A @30 VDC 70,000 ops (10
ops/minute) at 75°C
5 A @250 VAC/30 VDC 6,000 ops
5 A @250 VAC/30 VDC 6,000
ops
Electrical Life
(Resistive load)
UL
3 A @250 VAC/30 VDC 100,000
ops
3 A @250 VAC/30 VDC 100,000
ops
Mechanical Life
20,000,000 ops at no load (300
ops/minute)
20,000,000 ops at no load (300
ops/minute)
Power-on Value
Yes, Programmable
Yes, Programmable
Safe Value
Yes, Programmable
Yes, Programmable
Digital Input/Counter
Input Channels
3
Type
Wet Contact (Sink, Source)
On Voltage Level
+3.5 ~ +50 VDC
Off Voltage Level
+1 VDC max.
Input Impedance
10 K
Ω
, 0.66 W
Channels 3
Max. Count
65535 (16-bit)
Max. Input Frequency
100 Hz
Counters
Min. Pulse Width
5 ms
Over-voltage Protection
70 VDC
No Digital Input
Power Requirements
Reverse Polarity Protection
Yes
Powered from Terminal Block
Yes, 10 ~ 30 VDC
Consumption
0.6 W max
1.0 W max
tM Series DIO User Manual, Rev: A1.3 7PH-013-A13
16
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru
Summary of Contents for tM Series
Page 8: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 8 7 495 109 02 08 sales bbrc ru www bbrc ru...
Page 9: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 9 7 495 109 02 08 sales bbrc ru www bbrc ru...
Page 10: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 10 7 495 109 02 08 sales bbrc ru www bbrc ru...
Page 11: ...tM Series DIO User Manual Rev A1 3 7PH 013 A13 11 7 495 109 02 08 sales bbrc ru www bbrc ru...