2.12 $AA5
Description:
Reads the reset status of a module.
Syntax:
$AA5[CHKSUM](CR)
$
Delimiter
character
AA
Address of the module to be read (00 to FF)
5
Command to read the module reset status
Response:
Valid Command:
!AAS[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
S Reset status of the module
1: This is the first time the command has been sent
since the module was powered on.
0: This is not the first time the command has been
sent since the module was powered on, which
denotes that there has been no module reset since
the last $AA5 command was sent.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.