The following are examples of pair-connection tests:
Pair-connection Settings:
Model
Port Settings
(default)
Pair-connection Settings
Baud
Rate
Data
Format
Application
Mode
Remote
Server IP
Remote
TCP Port
(default)
tDS-700 #1
115200
8N1
Client
IP Address of tDS-700 #2
10001
tDS-700 #2
115200
8N1
Server
-
-
Note
The Baud Rate and Data Format settings of the client and server (tDS-700 #1 and #2)
depend on the COM ports of the PC (or the connected device). The serial port settings
between tDS-700 #1 and tDS-700#2 can be different.
Follow the procedure described below:
Step 1: Connecting to a network, PC and Power
1.
Confirm that the tDS-700 modules are functioning correctly. Refer to
Chapter 3 Setting up the
tDS-700 module
for more details.
2.
Use a DN-09-2F wiring terminal board to connect COM1 of the PC to COM1 of the tDS-700 #1.
For detailed RS-232 wiring information, refer to
section
2.7 “Wiring Notes
for RS-232/485/422
Interfaces
”
.
(DN-09-2F Web site:
http://www.icpdas.com/products/DAQ/screw_terminal/dn_09_2.htm
)
3.
Use a i-7520 module to connect COM2 of PC to COM1 of the tDS-700 #2. For detailed RS-
422/485 wiring information, refer to
section
2.7 “Wiring Notes
for RS-232/485/422 Interfaces
”
.
(i-7520 Web site:
http://www.icpdas.com/products/Remote_IO/i-7000/i-7520.htm
)
※
Refer to
Figure 5-1
for an illustration of how to perform the above steps.