![ICP DAS USA PETL Series User Manual Download Page 24](http://html1.mh-extra.com/html/icp-das-usa/petl-series/petl-series_user-manual_3886670024.webp)
Ethernet I/O Modules
ICP DAS CO., LTD.
PETL/tET/tPET DIO Series User Manual, Ver. 2.2, Aug. 2017, Page: 24
PETL-7060
Models
PETL-7060
Digital Input
Input Channels
6
Input Type (Device)
Wet Contact (Sink, Source)
On Voltage Level
+10 V
DC
~ +50 V
DC
Off Voltage Level
+4 V
DC
Max.
Input Impedance
10 k
Ω
Counters
Max. Count
4,294,967,285 (32 bits)
Min. Pulse Width
0.15 ms
Frequency Measurement
3.5 kHz (without filter)
Overvoltage Protection
+70 V
DC
Isolation
3750 V
rms
Relay Output
Output Channels
6
Output Type (Module)
Power Relay, Form A (SPST N.O.)
Output Voltage Range
250 V
AC
/30 V
DC
Max. Load Current
5.0 A/channel
Operate Time
6 ms
Release Time
3 ms
PWM
50 Hz max. (The
High/Low duty cycle range = 10 ~ 65,535 ms)
Electrical Life
(Resistive load)
VED
5 A 250 V
AC
30,000 ops (10 ops/minute) at 75 °C
5 A 30 V
DC
70,000 ops (10 ops/minute) at 75 °C
UL
5 A 250 V
AC/
30 V
DC
6,000 ops
3 A 250 V
AC/
30 V
DC
100,000 ops
Mechanical Life
20,000,000 ops. At no load (300 ops./ minute)
Output Isolation
3000 V
rms
Note
Because of the characteristics of the relay functions, it is recommended that the PWM on
t(P)ET-P(D)2POR2/ t(P)ET-P2R2/ t(P)ET-PD2R1/ PETL-7060 series modules (i.e., modules with relay
functions) is not used for extended periods of time.