M-7084 User Manual, Rev. A1.3 7PH-013-A13
90
Examples:
Command: @01FT0A
Response: !01
Sets the frequency measurement timeout for module
01 to 1 second and returns a valid response.
Related Commands:
Section 2.30 @AAFT
Related Topics:
Section A.6 Frequency Measurement
Note:
1.
The command is only available to the channels that are set
to type code 51, frequency measurement.
2.
If there is no input pulse detected during the frequency
measurement time out, then the frequency of the channel is
set to 0 Hz.