M-7084 User Manual, Rev. A1.3 7PH-013-A13
31
2.1 %AANNTTCCFF
Description:
Sets the configuration of a module.
Syntax
:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
Address of the module to be configured in
hexadecimal format (00 to FF)
NN
New address of the module in hexadecimal format (00
to FF)
TT
New type code. Not used by the M-7084. It should
be set to 00 for the M-7084
CC
New Baud Rate code, see Section 1.9 for details. The
INIT* pin must be connected to ground in order to
change Baud Rates. For the module with frame
ground, this is achieved by moving the rear slide
switch to the INIT position. See Section A.1 for
details.
FF
Used to set the data format and checksum (Section
1.9). The INIT* pin must be connected to ground in
order to change the checksum setting. For the module
with frame ground, this is achieved by moving the rear
slide switch to the INIT position. See Section A.1 for
details.