ET-2200 Series Ethernet I/O Modules
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
-
95 -
190
(0xBE)
1 to nDI
Enables frequency measurement for all
DI Channels
1
0 = Disable
1 = Enable
(Default= 0)
R/W/F
235
(0xEB)
1 to nDO
Sets the Power-on value for all DO
Channels
1
0 = Off
1 = On
(Default= 0)
R/W/F
267
(0x10B)
1 to nDO
Sets the Safe value for all DO Channels
1
0 = Off
1 = On
(Default= 0)
R/W/F
299
(0x12B)
1
Force the DI/DO Mode.
(for the ET-2254
only)
0 = Dynamic I/O type based on DO
requests.
1 = Static I/O type by configuration (web
or Modbus).
1
0 = Dynamic
1= Static
R/W
300 ~ 315
(0x12C ~
0x13B)
1 to UDIO
Sets the Universal DIO channels to DI or
DO Port.
(for the ET-2254 only)
300 is the CH0 address, 301 is the CH1
address, and so on.
1
0 = DO type
1= DI type
R/W
Notes
R
: ‘ead
W
: Write
F
: “etti g
s are recorded in flash by default
E
: A
fter writing DO[60] register, the data will be stored in flash.
Warning:
Frequency writing to the Flash can cause it to become corrupt.
Because of the characteristics of the relay functions, it is recommended that the PWM on
ET-2260/2261/2268 series (i.e., modules with relay functions) is not used for extended periods
of time.