ET-2200 Series Ethernet I/O Modules
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
-
84 -
6.2.5 05(0x05) Force a Single Coil (Write DO)
This function code is used to set the status of a single coil or a single digital output value for the
ET-2200 series module.
[Request]
Byte
Description
Size
Value
00
Net ID (Station Number)
1 Byte
1 to 247
01
Function Code
1 Byte
0x05
02-03
DO Address
2 Bytes
Refer to the Modbus Address Table (
) for the
ET-2200 series module.
Byte 02 = high byte
Byte 03 = low byte
04-05
Output Value
2 Bytes
0xFF 00 sets the output to ON.
0x00 00 sets the output to OFF.
All other values are invalid and will not
affect the coil.
Byte 04 = high byte
Byte 05 = low byte
[Response]
Byte
Description
Size
Value
00
Net ID (Station Number)
1 Byte
1 to 247
01
Function Code
1 Byte
0x05
02-03
DO Address
2 Bytes
The value is the same as Bytes 02-03 of the
Request
04-05
Output Value
2 Bytes
The value is the same as Bytes 04-05 of the
Request
[Error Response]
Byte
Description
Size
Value
00
Net ID (Station Number)
1 Byte
1 to 247
01
Function Code
1 Byte
0x85
02
Exception Code
1 Byte
Refer to the Modbus Standard
Specifications for more details.
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru