ET-2200 Series Ethernet I/O Modules
Copyright © 2016 ICP DAS CO., Ltd. All Rights Reserved.
-
45 -
Item
Description
Digital Output
Host Watchdog Timeout
(Seconds)
This parameter is used to configure the Host Watchdog timeout value.
If
there is no Modbus TCP communication activity for the specified period
(the timeout), then the Host Watchdog will activate an alarm.
Enable Watchdog
This parameter is used to enable the watchdog on each DO channels.
Safe Value
This parameter is used to define the DO safe value for the ET-2200
module. If the Host Watchdog alarm is activated, the DO will be set to
the user-defined safe value.
Power-On Value
This parameter is used to define the DO Power-on value. On boot up, the
DO is set to the user-defined Power-on value.
Digital Input
Enable Latched DI
This parameter is uses to enable the latch function on all DI channels.
The status of the DI will be recorded if it has been flagged as either high
or low.
0 = Disable All; 1 = Enable All
Clear Latched Status
(High)
This parameter is used to clear the status of all high latched D/I.
0 = No Operation; 1 = Clear All
Clear Latched Status
(Low)
This parameter is used to clear the status of all low latched D/I.
0 = No Operation; 1= Clear All
DI Filter Level
The DI filter is a function that eliminates high-frequency noise from
inputs.
Settings range value: 1 ~ 6500 (ms); 0 = Disable (Default).
Refer to
FAQ004_What is Digital-Input Filter (DI Filter)
for more
detailed information.
Digital Counter
Enable Digital Counter
This parameter is used to enable the digital counter on each DI channels.
Clear Digital Counter
This parameter is used to clear the values of each DI counters.
Preset Counter Value
This parameter is used to set the default value for each DI counters.
Frequency Measurement by DI
Enable
Frequency
Measurement
This parameter is used to enable the frequency measurement function
on each DI channels.