iCON iPROTECT Instruction Manual Rev 4.4
7
Rated power output
to the pump (P1 power)
Range 0 – 2.99kW
Default setting is 3.00kW
Button Press calibration saves the running value to this location
The trip response ratio of the
dry-running (underload)
protection
as a percentage of the rated current
Range 0 – 95%
Default setting is 70%
Control by means of a float attached directly to the pump: set to
0%
.
The trip response ratio of the
Overload Protection
as a
percentage of the rated current.
Range 0 – 135%
Default setting is 135%
The trip response ratio of the
Pump-Stalled Protection
as a
percentage of the rated current.
Range 0 – 240%
Default setting is 200%
A pump-stalled event is a ‘critical error’ and has no auto-restart time
The trip voltage of the
Under Voltage Protection
(V)
Range 0 – 192V
Default setting is 176V
The trip voltage of the
Over Voltage Protection
(V)
Range 0 – 276V
Default setting is 253V
Note: Only Applicable to Drainage Mode
Anti-seize parameter.
In auto mode, if pump has not run for XX hours, controller will run the
pump for 3 seconds.
Range 0 – 254 hours
Default setting is 240 hours.
LCD Button operation lock function
00 = LCD and button function inactive
01 = LCD and button function activated
Default setting is 00 = inactive
If this function is activated, to unlock the controller hold MODE button then
press and hold the STORE/SET button. The controller will count down 6 – 10
seconds. Release all buttons and the controller will switch to manual mode
with all buttons unlocked