12
iCON iProtect Instruction Manual Rev 4.4
13. Transfer Mode - LCD running state images
Source liquid is below
the low-level setting.
The pump will not run.
Source liquid is above
the high-level setting
Pump available to run
Destination liquid below the
low-level setting.
If there is sufficient liquid at
the source the pump will
start
Destination liquid is above
the high-level setting.
The controller will turn the
pump off
The iProtect has a reliable automatic
stop function against pump dry-run.
When used with pumps where it is
inconvenient to install source floats
or probes, the installer can fit jumpers
between terminals 4,5 and 6.
Pump calibration:
(see pg 5)
Switch to manual mode 10 sec.
Start the pump
Allow the pump to reach a stable power.
Press to store. Press to exit.
Ensure the controller is set to
AUTO MODE when finished