Table 3: Chillgard Database Mapping
Database
Address
+0
+2
+4
+6
0
I/O State
Alarm Data
Audio
Preferences
Status
8
S1 Gas
Number
S1 Gas
Concentration
S1 Alarm
State
Reserved
16
S2 Gas
Number
S2 Gas
Concentration
S2 Alarm
State
Reserved
24
S3 Gas
Number
S3 Gas
Concentration
S3 Alarm
State
Reserved
32
S4 Gas
Number
S4 Gas
Concentration
S4 Alarm
State
Reserved
40
S5 Gas
Number
S5 Gas
Concentration
S5 Alarm
State
Reserved
48
S6 Gas
Number
S6 Gas
Concentration
S6 Alarm
State
Reserved
56
S7 Gas
Number
S7 Gas
Concentration
S7 Alarm
State
Reserved
64
S8 Gas
Number
S8 Gas
Concentration
S8 Alarm
State
Reserved
I/O State
This parameter is the I/O state of the monitor module overall. It may have the
following values:
0 – Warmup
1 – Ready
2 – Trouble
3 – Cal / Setup
Alarm Data
This parameter provides alarm information for the monitor module overall. This is
a bit-wise parameter with the following bit mapping:
Bit 6 – Audio On
Bit 7 – Alarm Latched
Audio Preferences
This parameter provides audio and latching preferences that are currently
configured for the monitor module. This is a bit-wise parameter with the following
bit mapping:
Bit 0 – Latching Caution Relay
Bit 1 – Latching Warning Relay
Bit 2 – Latching Alarm Relay