1. Push the sides of the lower half of the front side of the chassis (do not
push on any of the modules or module handles).
2. Chassis mounting brackets.
3. Rack vertical mounting rails.
4. Bottom support rails
Tip:
To adjust the placement of the chassis on the bottom-support rails, you
can use the handles on the sides of the chassis.
5.
If the mechanical lift is raised above the height of the bottom-support rails,
gently lower it to the level of the rails or no more than 1/4 inch (0.6 cm)
below the rails. This action helps to prevent the bottom of the chassis from
getting caught on the bottom expansion edges of the bottom-support rails.
Figure 32. Moving a Chassis onto a Rack or Cabinet - SAN768C-6 Chassis
Chapter 3. Installing the IBM c-type SAN Device
67
Summary of Contents for SAN192C-6
Page 2: ......
Page 8: ...vi SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 10: ...viii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 24: ...xxii SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 114: ...90 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 122: ...98 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 143: ...Figure 47 AJK2 Figure 48 AJK1 Figure 49 AJJY Appendix B Cable and Port Specifications 119 ...
Page 144: ...Figure 50 AJJV 120 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 146: ...122 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 158: ...134 SAN192C 6 SAN384C 6 and SAN768C 6 Installation Service and User Guide ...
Page 159: ......
Page 160: ...IBM Part Number 02JD693 Printed in USA SC27 9276 00 1P P N 02JD693 ...