If
Then
No:
Continue with step 5.
2.
Does the baseboard management controller (BMC) respond to commands?
Note:
To determine whether the BMC responds to commands, run the following
ipmitool
command:
ipmitool -I lanplus -U <username> -P <password> -H <bmc ip or bmc hostname> chassis status
If
Then
Yes:
Continue with the next step.
No:
Continue with step 4.
3.
Complete the following actions:
a.
Use the BMC to update the system firmware. For instructions, see Updating the system firmware
by using the BMC.
b.
Check the system event logs. For instructions, see “Identifying a service action by using system
event logs” on page 27. Then, continue with step 5.
4.
Complete the following actions, one at a time, until the problem is resolved:
a.
Reset the BMC remotely by entering the following command:
ipmitool -I lanplus -U <username> -P <password> -H <bmc ip or bmc hostname> mc reset cold
b.
Disconnect the power cords from the system for 30 seconds. Reconnect the power cords, wait 5
minutes, and then go to step 2.
c.
Use the IPMI tool to update the system firmware. For instructions, see Updating the system
firmware by using the IPMI tool.
d.
Complete the service action that is indicated for your system:
v
If your system is an 8335-GCA or 8335-GTA, replace the system backplane. Go to “8335-GCA
and 8335-GTA locations” on page 111 to identify the physical location and the removal and
replacement procedure.
v
If your system is an 8335-GTB, replace the BMC card. Go to “8335-GTB locations” on page 121
to identify the physical location and the removal and replacement procedure.
v
If your system is an 8348-21C, replace the system backplane. Go to “8348-21C locations” on
page 133 to identify the physical location and the removal and replacement procedure.
This ends the procedure.
5.
Are you here because of a system event log (SEL) with the value OEM record c0 and OEM c0
specific log information 3a1503xxxxxx?
If
Then
Yes:
Continue with step 8 on page 6.
No:
Continue with the next step.
6.
Are you here because of a SEL event with the value OEM record c0 and OEM c0 specific log
information 3a1504xxxxxx?
If
Then
Yes:
Continue with step 12 on page 7.
No:
Continue with the next step.
7.
Power off the system and disconnect all ac power cords for 30 seconds. Then, reconnect the ac
power cords and power on the system. Does the system boot successfully?
Beginning troubleshooting and problem analysis
5