15.
Insert the new front cage plane/midplane by aligning it with the storage
subsystem front opening and slowly sliding it into the storage subsystem
chassis. Make sure that the front cage frame EMC gaskets do not snag
between the frame and chassis.
16.
Tighten the four front cage frame screws. See Figure 86 on page 152.
17.
Install the seven Phillips screws (three on top and four on bottom) that hold
the front cage frame to the EXP810 chassis that you removed in step 12 on
page 152, as shown in Figure 87 on page 153.
18.
Push the chassis all the way back into the rail and install the four M5 screws
along the side edges of the DS3950 chassis.
19.
Install the four Phillips screws on the back along the sides of the DS3950
chassis that hold the DS3950 to the rails.
20.
Insert the E-DDM CRUs. Be sure you insert them in the correct slots. Use the
labels you put on them before you removed them to guide you.
21.
Re-insert the controllers and reconnect the Fibre Channel cables.
22.
Re-insert the power supply and fan units and reconnect the power supply
cords.
23.
Turn on the power to the attached storage expansion enclosures.
24.
Wait at least 3 minutes and then turn on the power to the DS3950 storage
subsystem. Verify the status of the configuration using LEDs and the DS
Storage Manager client program.
25.
After removing the faulty cage frame with midplane assembly, transpose the
DS3950 serial number, machine type, and model tag from the faulty cage
frame assembly to the Repair Identification (RID) tag on the new cage frame
assembly. The RID tag is important in transferring the serial number, machine
type, and model from the faulty cage frame assembly to the new cage frame
assembly. Make sure that the new RID tag is affixed to the new cage frame
assembly before you dispose of the faulty cage frame with midplane assembly.
This will so that the warranty coverage is not interrupted.
154
IBM System Storage DS3950 Storage Subsystem: Installation, User’s, and Maintenance Guide
Summary of Contents for DS3950
Page 2: ......
Page 8: ...vi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 12: ...x IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 28: ...xxvi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 54: ...26 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 148: ...120 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 202: ...174 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 210: ...182 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 214: ...186 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 226: ...198 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 246: ...218 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 250: ...222 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 251: ......
Page 252: ...Part Number 00Y5046 Printed in USA GA32 0953 03 1P P N 00Y5046...