Attention:
Although the link rate LED indicates the correct speed setting,
the link rate speed does not change until after you cycle power to the
storage subsystem.
6.
Repeat step 1 on page 139 through step 5 on page 140 for all of the storage
subsystems in the configuration.
7.
Perform the power-on sequence as described in “Turning on the storage
subsystem” on page 95.
8.
Check the indicator lights on the front and back of all of the storage
subsystem and expansion drive modules. All the green indicator LEDs are lit,
and the amber indicator LEDs are off. (No LEDs are displayed on blank
drives.)
9.
Are
only
the green indicator LEDs on?
v
Yes
- The drive is working correctly.
v
No
- If an amber Fault indicator LED is on, go to 10.
10.
Diagnose and correct the fault.
a.
To run the Recovery Guru, select the Recovery Guru toolbar button in the
Subsystem Management window.
b.
Complete the recovery procedure.
c.
When the procedure is completed, rerun the Recovery Guru to make sure
that the problem has been corrected by selecting Recheck in the Recovery
Guru.
11.
If the problem persists, contact IBM Customer and Technical Support.
Replacing an ac power supply and fan unit
Statement 5:
CAUTION:
The power control button on the device and the power switch on the power
supply do not turn off the electrical current supplied to the device. The device
also might have more than one power cord. To remove all electrical current from
the device, ensure that all power cords are disconnected from the power source.
1
2
CAUTION:
Disconnect the power cord before replacing the power supply and fan unit.
The power supply and fan unit is a component that includes both a 600-W power
supply unit and two fans. The power supply and fan units provide power and
cooling for the DS3950. The power supply and fan units are customer replaceable
units (CRUs) and do not require preventive maintenance. Use only the supported
power supply and fan units for your specific storage subsystem.
Chapter 5. Replacing components
141
Summary of Contents for DS3950
Page 2: ......
Page 8: ...vi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 12: ...x IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 28: ...xxvi IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 54: ...26 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 148: ...120 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 202: ...174 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 210: ...182 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 214: ...186 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 226: ...198 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 246: ...218 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 250: ...222 IBM System Storage DS3950 Storage Subsystem Installation User s and Maintenance Guide...
Page 251: ......
Page 252: ...Part Number 00Y5046 Printed in USA GA32 0953 03 1P P N 00Y5046...