Table 1 shows the weight and dimensions of the 5066 Expansion Unit.
Table 1. 5066 Weight and Size descriptions
Weight (fully configured)
1600 lb (725 kg)
Width
25.5 in (650 mm)
Depth
40 in (1020 mm)
Height
71 in (1800 mm)
The 5066 has a floor loading of 86 lb/ft
2
(420 kg/m
2
). Because of the size and
weight of the 5066, you should do the following:
CAUTION:
Overlapping the clearance defined below with adjacent equipment results in a
significant increase in the amount of floor loading.
v
Contact your facility or structural engineer to determine a safe site for your
5066.
v
Leave 30 in. (762 mm) of clearance to the front and back of the 5066.
v
Leave 5 in. (127 mm) of clearance to the left and right of the 5066.
Planning your cable layout
When you decide where to place your cables, follow your site plan and keep the
following things in mind:
v
Avoid creating a safety hazard.
v
Avoid damaging the cable.
Placing power cords for the 5066
You need to provide the appropriate receptacles for the power cords shipped with
your 5066. The usable length of the upper power cord is 4 ft. (1.2 m) shorter than
the length of the lower power cord.
Redundant links
Your new expansion unit has disk units. Therefore, when you plan your cable
layout, you should use a redundant link configuration to protect your disk units. A
redundant link
is a secondary optical cable link that your system can use if the
primary link experiences a failure. You can create a redundant link configuration
by connecting an extra optical cable link between the expansion units and the
system unit.
Refer to Figure 1 on page 3 to see how to plan your cables with a redundant link
configuration with one expansion unit. If you are linking two expansion units refer
to Figure 2 on page 3 If you are setting up a 5066, refer to Figure 3 on page 4.
2
Setting Up Your 5065 or 5066 Expansion Unit V4R5
Summary of Contents for AS/400e
Page 1: ...AS 400e Setting Up Your 5065 or 5066 Expansion Unit V ersion 4 SA41 5146 01...
Page 2: ......
Page 3: ...AS 400e Setting Up Your 5065 or 5066 Expansion Unit V ersion 4 SA41 5146 01...
Page 6: ...iv Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 10: ...viii Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 28: ...16 Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 30: ...Figure 19 Opening the 5066 rear cover 18 Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 36: ...24 Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 46: ...34 Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 80: ...68 Setting Up Your 5065 or 5066 Expansion Unit V4R5...
Page 83: ......
Page 85: ...Spine information AS 400e Setting Up Your 5065 or 5066 Expansion Unit V4R5 Version 4...