Figure 24
Top view - minimum distance of exhaust vent to inside and outside corners
Warning
In areas of high snowfall, users must be advised to check side wall vent and air intake
terminations on a regular basis to ensure blockage does not occur.
Sidewall direct vent with stainless sidewall terminal must be terminated as follows:
The Stainless Sidewall Terminal (SST) 2 inch (IBC kit P-256 ) or 3 inch (IBC kit P-257 ) are
approved for use with this appliance.
Install the SST to comply with the minimum vent clearances listed in
.
Install the SST with the vent and intake pipes horizontally beside each other or vertically with
the vent pipe on top (see
). The vent pipe cannot be installed below the intake. The
vent cap must be installed with the openings directed up and down (see
), and not
side to side.
Figure 25
Allowed SST installation orientations
The SST vent/air connections fit Sched. 40 two inch or three inch PVC/CPVC pipe. PPs
pipe cannot be used with the SST. The pipes must extend completely through the wall as
shown below. The SST is an external fixture, and is not part of the sealed vent system that
runs inside the building.
33
3.7.6 Sidewall vent termination
Summary of Contents for VX Series
Page 8: ...Intentionally left empty...
Page 14: ...Intentionally left empty...
Page 52: ...Figure 36 Two pump two load parallel piping concept 48 Section Installation...
Page 74: ...Intentionally left empty...
Page 100: ...Intentionally left empty...
Page 101: ...97 Appendices Wiring diagrams Figure 48 Controller electrical diagram...
Page 102: ...Figure 49 Internal wiring diagram 98 Section Appendices...
Page 103: ...Figure 50 Sequence of Operation 99 Appendices...
Page 106: ...102 Section Appendices...