INSTALLATION AND OPERATION INSTRUCTIONS
3-4
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
3.4 FUEL CONVERSION
The SL modulating boilers are factory fire-tested to operate with natural gas, or propane
as ordered. The rating plate will be marked to indicate which fuel the particular boiler
has been set up with. Firing a boiler with a fuel other than what is listed on the rating
plate is prohibited unless the following conversion procedure is completed by a qualified
technician.
Refer to the preceding section 3.3 - COMMISSIONING. The Zero-offset valve adjustment
cap on the gas valve has been factory sealed using red paint-seal compound.
This cap
must not be tampered with. The Zero-offset screw is not to be adjusted in the field.
Fuel conversion requires hardware adjustments (orifice insertion or removal) as well as
measurement and possible tuning of the gas:air mixture. Detailed instructions including parts
and labeling are found in the Fuel Conversion kits.
Fuel conversions must be carried out by a qualified technician:
1. Ensure you are installing the correct fuel conversion kit for your boiler. Compare the
boiler model number with the Kit # found in Table 8.
2. Read the fuel conversion instructions supplied with the fuel conversion kit.
3. Carefully follow the procedures of the fuel conversion instructions on:
•
Fuel Conversion
•
Combustion Testing and Adjustment
•
Placing conversion labels associated with the new fuel onto the boiler.
4. Carefully follow the
“Prior to Start-Up” – Section 3.2 and “Commissioning” – Section
3.3 procedures on the preceding pages 3-2 and 3-3.
Fuel Conversion Kit Part Numbers
MODEL NUMBER
NATURAL GAS TO
PROPANE
PROPANE TO
NATURAL GAS
SL 10-85 G3/ SL 14-115 G3 P-304
P-305
SL 20-160 G3
P-306
P-307
SL 30-199 G3
P-308
P-309
Table 8: Fuel Conversion Kits
DANGER
Operating any IBC boiler using
a fuel other than the fuel listed
on its rating plate is prohibited.
If the information in this section
related to conversion to
alternate fuels is not followed
exactly, a dangerous situation
can result, leading to fire or
explosion, which may cause
property damage, personal
injury, or loss of life.
Summary of Contents for SL 20-160 G3
Page 75: ...6 3 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 77: ...6 5 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 79: ...6 7 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 85: ...SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...
Page 86: ...NOTES...
Page 87: ...NOTES...