3
INSTALLATION AND OPERATING INSTRUCTIONS
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
SPECIFICATIONS
SPECIFICATION
SL 10-85 G3
SL 14-115 G3
SL 20-160 G3
SL 30-199 G3
CSA Input (Natural Gas or Propane*) - MBH
CSA Input (Natural Gas or Propane*) - kW
CSA Output - MBH
CSA Output - kW
10.6 - 85
3.10 - 24.9
10.1 - 79
2.96 - 23.1
14 - 115
4.10 - 33.7
13.3 - 109
3.90 - 32.0
20 - 160
5.86 - 46.9
19.0 - 147
5.57 - 43.1
32 - 199
9.37 - 58.3
30 - 181.3
8.8 - 53.1
A.F.U.E.
96%
95%
95%
95%
Minimum gas supply pressure (Natural Gas or Pro
-
pane) - inch w.c.
4
4
4
4
Maximum gas supply pressure (Natural Gas or
Propane) - inch w.c.
14
14
14
14
Power use (120Vac/60Hz) @ full fire - Watts (without
pumps)
54
72
82
100
Weight (empty) - lbs/Kg
85 / 39
85 / 39
102 / 46.3
152 / 69
Pressure vessel water content - USG/Litres
2.47 / 9.35
2.47 / 9.35
1.72 / 6.51
5.09 / 19.3
Maximum boiler flow rate - USgpm
14
14
19
22
Minimum boiler flow rate - USgpm
2
2
4
6
Maximum operating water pressure† - psig
30
30
30
30
Minimum water pressure - psig
8
8
8
8
Approved installation altitude - ASL
0 - 12,000’
0 - 12,000’
0 - 12000’
0 - 12,000’
Ambient temperature - Low (°F-°C)
Ambient temperature - High (°F-°C)
32°F / 0°C
122°F / 50°C
32°F / 0°C
122°F / 50°C
32°F / 0°C
122°F / 50°C
32°F / 0°C
122°F / 50°C
Max. relative humidity (non-condensing)
90%
90%
90%
90%
Minimum water temp.
34°F / 1°C
34°F / 1°C
34°F / 1°C
34°F / 1°C
Maximum water temp. (electronic hi-limit)
190°F / 88°C
190°F / 88°C
190°F / 88°C
190°F / 88°C
Maximum water temp. lockout limit
201°F / 94°C
201°F / 94°C
201°F / 94°C
201°F / 94°C
Max. ΔT - supply/return (electronic fence)
40°F
40°F
40°F
40°F
Maximum equivalent vent length, each side (vent
and air intake - 2”
(Natural Gas or Propane -3”
Air intake options: either direct vent or indoor sup
-
ply
100’
240’
100’
240’
35’
170’
N/A
150’
Summary of Contents for SL 20-160 G3
Page 75: ...6 3 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 77: ...6 5 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 79: ...6 7 DIAGRAMS SL 10 85 G3 SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 85: ...SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...
Page 86: ...NOTES...
Page 87: ...NOTES...