ibaClock
Manual
Issue 1.4
13
7.2
Display elements
The operating status of the device is shown by colored status LEDs.
Operating state
LED Color
State
Description
Run Green
Flashes slowly
Flashes quickly
Off
Ready for use, power supply is applied to
Programming mode, e.g. at a firmware update
Out of service, no voltage supply
-
Yellow
-
Without function
Link White
On
Flashes
Off
Valid signal at RX
Signal at RX, but configuration deviates from the detected
signal
No signal at RX
Error Red
Flashes
Off
Error message
Error-free operation
Status of time sources
The LED of the activated time source is always the only one activated (currently GPS).
Every LED can accept the following statuses:
Status
Description
Off
Time source not selected
Green
Time source OK
Flashes green
Synchronization to time source or time source disrupted
Red
Time source defective
7.3
Connections
7.3.1
FO connections X10 (TX) and X11 (RX)
X11 (RX): FO receive interface
X10 (TX): FO send interface
A bidirectional FO connection is required for the connection to an ibaPDA system. A FO
card type ibaFOB-D or ibaFOB-Dexp has to be installed in the ibaPDA computer so
that data can be received and sent.
The interfaces are made for cables with 62.5/125 μm multimode fibers with ST connect-
ors. Suitable FO patch cables are available at iba.
7.3.2
Power supply X14
The 2-pin input serves for the supply of the device with DC 24 V ±10% (non regulated).
The operating voltage should be put in via the supplied Phoenix threaded coupling con-
nector. If requested, you can also order DIN rails or plug-in power supply units at iba.