![IBA ibaBM-DDCS Manual Download Page 45](http://html1.mh-extra.com/html/iba/ibabm-ddcs/ibabm-ddcs_manual_3210872045.webp)
ibaBM-DDCS
Manual
Issue 1.11
45
10
Technical data
10.1 Main data
Short description
Name
ibaBM-DDCS
Description
Bus monitor for DDCS drive bus
Order number
13.120710
DDCS interface
Number
3 for one DDCS drive bus
Design
2 HBFR Versatile Link connector (1 mm POF) for RX and
TX, simplex, duplex, without interlocking (per link)
Typical application
Link0: Connected with control (only Rx is used here)
Link1: Connected with measurement interface of the drives
Link2: Connected to computer with DriveWindow for
configuration and measurement, if required
ibaNet interface
Number
1 (e.g. connection to ibaPDA)
ibaNet protocol
32Mbit Flex
Data transmission rate
32 Mbit/s
Sampling rate
Up to 40 kHz, freely adjustable
Connection type
2 ST connector (62.5 µm / 125 µm), cable length up to
2000 m without repeater
Power supply, operating and indicating elements
Power supply
+24 V DC (±10 %)
Power consumption
Up to 15 W
Rotary switch
Device address (in a cascade)
Indicators
4 LEDs for the operating status
8 LEDs for the channel status
Operating and environmental conditions
Cooling
Passive
Operating temperature
32 °F to 122 °F (0° C to 50° C)
Storage and transportation temperature
-13 °F to 158 °F (-25° C to 70° C)
Humidity class according to DIN 40040
F, no condensation
Protection class
IP20
Mounting
DIN rail , vertical
Standards
EMC: IEC 61326-1
FCC part 15 class A