background image

 

Manual 

ibaBM-DDCS 

 

16

 

Issue 1.11 

 

 

ibaBM-DDCS in ABB environment 

8.1 

Configuration with data set and parameter channel  

 

Figure 2: 

ibaBM-DDCS in the ABB environment with ABB control 

 
ibaBM-DDCS offers 2 options for capturing and recording measured signals: 

1. 

Logging of the signals in the data set channel (CH0 connection of the drives). 

Simplex

 fiber optic connection between ibaBM-DDCS X30 and an arbitrary channel 

of the NDBU-95 (NDBU operation mode: “REGEN”). The X31 output must not be 

connected to the NDBU-95. 

Alternative connection: ibaBM-DDCS is integrated in the connection between 

NDBU-95 and ABB control. 

2. 

Querying of other values  from the drives in the parameter  data channel (CH3 

connection of the drives). 

Duplex

  fiber optic connection between ibaBM-DDCS 

X32/X33 and the CH3  port  of a drive or the MSTR port  of a NDBU-95  (NDBU 

operation mode: “DDCS/DRIVEBUS”). 

3. 

Furthermore, ibaBM-DDCS offers a connection to  loopthrough configuration and 

measurement queries of an external computer with DriveWindow. The DriveWindow 

computer is connected to the drives via the parameter channel if needed. 

Duplex

 

fiber optic connection between ibaBM-DDCS  X34/X35 and the DriveWindow 

computer. 

 
 

Summary of Contents for ibaBM-DDCS

Page 1: ...ibaBM DDCS Manual Issue 1 11 1 ibaBM DDCS Bus monitor for the DDCS drive bus from ABB Manual Issue 1 11...

Page 2: ...red trademark of the Microsoft Corporation Other product and company names mentioned in this manual can be brands or trade names of the corresponding owners Certification The device is certified accor...

Page 3: ...er side 12 7 5 Device layout 13 7 5 1 Operating status display status LEDs 1 13 7 5 2 Status LEDs data set query 2 14 7 5 3 Status LEDs parameter query 3 14 7 5 4 24 V power supply 4 14 7 5 5 X30 Rx 5...

Page 4: ...uration in the I O Manager 32 9 1 1 ibaBM DDCS General tab 33 9 1 2 ibaBM DDCS Diagnostics tab 35 9 1 3 Module type Data set 35 9 1 4 Module type Parameter 38 9 1 5 Module type Diagnose 40 9 1 6 Modul...

Page 5: ...of assessing safety and recognizing possible consequences and risks on the basis of his her specialist training knowledge and experience and knowledge of the standard regulations 1 2 Notation In this...

Page 6: ...ss and the system or machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The non o...

Page 7: ...ibaBM DDCS is handled by the bidirectional iba fiber optic protocol 32Mbit Flex which requires an I O card of the ibaFOB D generation e g ibaFOB 2io D The sampling rate can be up to 40 kHz whereby up...

Page 8: ...ibaBM DDCS 8 Issue 1 11 3 Scope of delivery The scope of delivery includes ibaBM DDCS device Manual 2 pin plug for power supply See www iba ag com for other accessories not included in the scope of de...

Page 9: ...ch cable duplex for connecting ibaBM DDCS and ibaPDA computer 4 2 Software ibaPDA V6 26 or higher for capturing recording and displaying the measurement data and for configuring the device ibaAnalyzer...

Page 10: ...perating voltage range Stay within the operating voltage range of DC 24 V 10 Do not open the device There are no components requiring maintenance in the device Opening the device voids your warranty N...

Page 11: ...Connect the power supply Observe the correct polarity 4 Connect the other cables 6 2 Disassembly 1 Disconnect the power supply 2 Disconnect all cables 3 Close the open fiber optic inputs and outputs w...

Page 12: ...e signals which are exchanged between controller and drive data set channel Active querying of additional measurements and parameters from the drives parameter channel Loopthrough of configuration and...

Page 13: ...itch S1 12 FO output X10 TX 13 FO input X11 RX Figure 1 Device layout 7 5 1 Operating status display status LEDs 1 LED Status Description Run green red red on green blinking off Device starting if the...

Page 14: ...f Connection for DriveWindow released Connection for ibaBM DDCS released Link yellow blinking Blinks when a message is received steadily lit when several messages are being received Resp white on blin...

Page 15: ...topology The devices are addressed via the rotary switch S1 Device numbers in the cascade Rotary switch position Not allowed 0 1st Device 1 2nd Device 2 14th Device E 15th Device F 7 5 9 Fiber optic...

Page 16: ...cted to the NDBU 95 Alternative connection ibaBM DDCS is integrated in the connection between NDBU 95 and ABB control 2 Querying of other values from the drives in the parameter data channel CH3 conne...

Page 17: ...ard in a fiber optic ring topology e g ibaPADU S IT ibaBM eCAT The rotary switch S1 has to be set to a unique device number at each device Keep in mind that the total data rate in the fiber optic ring...

Page 18: ...de a given measurement or status value with ABB The ABB control sends even data set numbers 2n to the drives which answer with the next odd data set number 2n 1 ABB control Drive Query response Data s...

Page 19: ...ed via a unidirectional FO cable to that NDBU 95 which is next to the controller This NDBU 95 must be operated in REGEN mode then the device can read all telegrams including the response telegrams sen...

Page 20: ...d and saved in the parameter APPLICATION MACRO of the set START UP DATA z B Par 99 03 Settings at the branching unit NDBU 95 Address settings S1 Address range 76 124 Default setting 01111100 0x7C S1 O...

Page 21: ...es DDCS branching unit are used to distribute the DDCS telegrams 8 drives can be connected to each NDBU 95 Up to 16 NDBU 95 devices can be cascaded The device ibaBM DDCS is coupled into the FO connect...

Page 22: ...de Important note When acquiring data sets in a star topology ensure that the connected drives are set to Star topology In DriveWindow the parameter CH0 HW CONNECTION in the parameter set DDCS Control...

Page 23: ...s The telegrams are sent from one drive CH0 to the next one via a FO ring Every drive CH0 takes the data which are addressed to it from the data stream and sends the reply data to the next drive The l...

Page 24: ...data sets in a ring topology ensure that the connected drives are set to Ring mode In DriveWindow the parameter CH0 HW CONNECTION in the parameter set DDCS Control of each drive has to be checked and...

Page 25: ...via handshake request response by the drive the access cycle depends directly on the number of values which are requested A standard value is approx 2 ms per analog value and approx 2 ms per 16 digit...

Page 26: ...lished using a NDBU 95 in star or ring topology 8 4 2 Star topology Several drives can be accessed via one or more NDBU 95 devices DDCS branching unit 8 drives can be connected to each NDBU 95 Up to 1...

Page 27: ...ir POF Figure 10 ibaBM DDCS parameter in STAR topology Settings at the branching unit NDBU 95 Address settings S1 Address range 76 124 01001100 01111100 0x4C 0x7C Note When NDBU 95 units are cascaded...

Page 28: ...y A ring topology may often be found in older plants The telegrams are sent from one drive to the next one via a FO ring Every drive takes the data which are addressed to it from the data stream and s...

Page 29: ...third fiber optic connection for connecting an external computer with DriveWindow software The communication between the DriveWindow computer and the drives is looped through ibaBM DDCS there is no ac...

Page 30: ...tion status you can see the current number of bytes that are transferred Access via data set The data cycle depends on the limitation on the FO side which is described above Access via parameter As ev...

Page 31: ...lues which are set to Fast and 6 slow values The 2 fast values and 1 slow value are sent with each cycle in total 3 values Hence one cycle takes 6 ms Each slow value is captured in every 6th cycle tha...

Page 32: ...the I O Manager Click on the link with the right mouse button which opens a submenu Select Add module Another submenu with all available devices will be displayed Select ibaBM DDCS from this list ibaB...

Page 33: ...there is also the module type Data set telegram counters available Figure 14 Adding modules 9 1 1 ibaBM DDCS General tab Here you can see the standard settings for the device Figure 15 ibaBM DDCS Gen...

Page 34: ...ction If this is successful the measurement will be restarted FALSE the measurement is not started if ibaPDA cannot establish a connection to the device DDCS Data set speed CH0 You can select the spee...

Page 35: ...pdate file bmddcs_vxxx iba in the browser window and start the update with OK The procedure takes several minutes and must not be interrupted Reset to factory defaults Please note that configurations...

Page 36: ...ill be overwritten by the default value The default value can be preset in the Analog and Digital tabs False In the event of a timeout the last transmitted value will remain Module Layout No analog si...

Page 37: ...umber slave data set number and index are entered automatically Figure 19 Overview of the data set signals Complete control words status words and fault words can be captured as analog value and itemi...

Page 38: ...odified Locked True No changes possible Only authorized users can unlock modules False Any user can make changes Enabled True Data acquisition is enabled for this module False Data acquisition is not...

Page 39: ...o select the parameter signals click on Browse in the bottom field The parameter browser will open and the nodes drives will be displayed Only the active nodes drives will be displayed here In the tre...

Page 40: ...be applied to the device and the measurement will automatically start Note Make sure that a signal is not requested twice In case of duplicate signals ibaPDA displays the an error message when startin...

Page 41: ...ase used for this module Use name as prefix If TRUE is selected the module name is placed in front of the signal name as prefix The diagnose data is pre defined in the Analog and Digital tab The diagn...

Page 42: ...dules could be imported in the I O Manager Module 290 diagnostic counter for data set telegrams drive 1 16 Module 291 diagnostic counter for data set telegrams drive 17 32 Module 299 general diagnosti...

Page 43: ...drives 1 to 127 are pre defined in the Analog tab The telegram counters can be visualized and saved like measured values Figure 27 Data set telegram counters Analog tab 9 1 7 Display of the measured v...

Page 44: ...CS 44 Issue 1 11 Figure 29 Actual values of the digital signals All selected signals will be displayed in the ibaPDA signal tree You can capture and record the measurements as usual Figure 30 Measurem...

Page 45: ...er 1 e g connection to ibaPDA ibaNet protocol 32Mbit Flex Data transmission rate 32 Mbit s Sampling rate Up to 40 kHz freely adjustable Connection type 2 ST connector 62 5 m 125 m cable length up to 2...

Page 46: ...formation Unique Identifier 13 120710 ibaBM DDCS Responsible Party U S Contact Information iba America LLC 370 Winkler Drive Suite C Alpharetta Georgia 30004 770 886 2318 102 www iba america com FCC C...

Page 47: ...ibaBM DDCS Manual Issue 1 11 47 10 2 Dimension sheet Dimensions in mm Figure 31 Dimension sheet ibaBM DDCS Dimensions in mm Figure 32 Dimension sheet ibaBM DDCS with cables...

Page 48: ...product Contact Headquarters iba AG Koenigswarterstrasse 44 D 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 E mail iba iba ag com Mailing address iba AG Postbox 1828 D 90708 Fuerth Ger...

Reviews: