HV Diagnostics
Setting Manual Test Parameters
Steps
MS 1-MS 8
describe how to
set
manual mode test parameters
.
Step
Procedure
(Set Manual Test Parameters)
Example
MS 1:
SETUP
To set the waveform, frequency, or test duration,
select “SETUP” on bottom of “Manual Test” screen
MS 2:
SETUP:
Waveform
Select one of the following output modes:
•
Sine wave
•
Square wave
•
DC+
•
DC-
•
Vacuum Bottle Test
•
Sheath Test
•
Sheath Fault Location
MS 3:
Sinewave;
Squarewave:
SETUP:
Frequency
Set the frequency to as close to 0.1 Hz as
possible.
•
0.1 Hz/Auto: Recommended setting that
automatically maintains the frequency as close
to 0.1 Hz as possible
To correct entry select “CANCEL” at bottom of
display.
MS 4:
Vacuum Bottle
Test:
SETUP:
Trip Current
Rise Rate
Set the test “Duration”:
•
Min. = 5 seconds; Max. = 15 minutes
Set the test “Trip Current”:
•
Min. = 200 µA, Max. = 1000 µA
Set the test “Rise” rate:
•
Min. = 0.5 kV/s, Max. = 5.0 kV/s
MS 5
Sheath Test
Set the test “Duration/Timer”:
•
Min. = 1 minute; Max. = 15 minutes
Set the test “Trip Current”:
•
Min. = 0.1 mA, Max. = 5.0 mA
Manual Test Sine 0.1Hz
Timer: 30 min
MAIN
SETUP
Trip out on Arc
START
0.0
kV
Manual Mode Setup
CANCEL
Sinewave
Squarewave
DC+
DC-
Vacuum Bottle Test
Sheath Test
Sheath Fault Location
Select Waveform
Manual Mode Setup
Waveform: Sine
Select Frequency
CANCEL
0.1 Hz/Auto
0.08 Hz
0.06 Hz
0.04 Hz
0.02 Hz
0.09 Hz
0.07 Hz
0.05 Hz
0.03 Hz
0.01 Hz
Manual Mode Setup
Vacuum Bottle Test
CANCEL
OK
5m 0 s
1000µA
0.5 kV/s
Duration:
Trip Current:
Rise:
Manual Mode Setup
Waveform DC Negative
Set Duration/Timer
1 min
Set Trip Current
5.0 mA
CANCEL
OK