MK/MV – Medium Profile Series Unit Coolers (E206993_M)
6
1
RECEIPT OF EQUIPMENT
1.1
INSPECTION
All equipment should be carefully checked for damage or shortages as soon as it is received.
Each shipment should be carefully checked against the bill of lading. If any damage or shortage is
evident, a notation must be made on the delivery receipt before it is signed and a claim should
then be filed against the freight carrier.
1.2
LOSS OF GAS HOLDING CHARGE
Each unit cooler is leak tested, evacuated to remove moisture, and then shipped with a gas holding
charge. Absence of this charge may indicate a leak has developed in transit. The system should not be
charged with refrigerant until it is verified that there is no leak, or the source of the leak is located.
2
UNIT INFORMATION AND DIMENSIONS
2.1
MODELS COVERED
MK Series medium profile unit coolers.
MV Series medium profile unit coolers - low temperature.
The MK and MV series are designed for walk-in coolers with ceiling heights of 10 to 14 feet
that require high airflow. MK/MV unit coolers draw air through the coil and discharge it into
the room via the unit fans.
The MK series handles medium to low temperature requirements and has three defrost options –
air, electric, and hot gas. The MV series is designed for low temperatures requiring extra high air
discharge velocities. The MV unit coolers are only available with electric defrost.