MK/MV – Medium Profile Series Unit Coolers (E206993_M)
15
Table 5-1 MK ELECTRIC OR GAS DEFROST
MODEL
CFM
STANDARD
CIRCUITS
NOZZLE
R404A
NOZZLE
R407A
NOZZLE
R448A
MK14( )-60
3245
4
L-3/4
L-1/2
L- 3/4
MK14( )-82
3060
5
L-1
L-3/4
L-1
MK14( )-105
2960
5
L-1
L-1
L-1-1/2
MK24( )-120
6490
10
J- 1-1/2
L-1
L- 1-1/2
MK24( )-164
6120
10
J-2
J-1-1/2
J-2
MK24( )-210
5920
13
J-2-1/2
J-2
J-2-1/2
MK34( )-246
9180
15
G-3
G-2
G-3
MK34( )-315
8880
20
G-4
G-3
G-4
MK44( )-420
11840
20
G-5
G-4
G-5
MK16( )-76
2985
4
L- 3/4
L-3/4
L-1
MK16( )-103
2815
5
L-1
L-1
L-1-1/2
MK16( )-127
2725
5
L-1-1/2
L-1-1/2
L-1-1/2
MK26( )-152
5970
10
J-2
J- 1-1/2
J-2
MK26( )-206
5630
10
J-2-1/2
J-2
J-2-1/2
MK26( )-254
5450
13
J-3
J-2-1/2
J-3
MK36( )-309
8445
15
G-4
G-3
G-4
MK36( )-381
8175
20
G-5
G-4
G-5
MK46( )-508
10900
20
G-6
G-5
G-6
Note:
Electric or hot gas defrost distributor nozzle selections are based on 20
°
F suction temperature,
10
°
F T.D. and 85
°
F liquid temperature. ( )-E, G, H, K, P.