MK/MV – Medium Profile Series Unit Coolers (E206993_M)
40
9.2.7 HOT GAS DEFROST
Notes:
1. The factory default setting for “Defrost Pump Down Time” is 2 minutes for hot gas defrost
units. This parameter may be adjusted in the field based on the specific application.
(liquid line length, location of liquid line solenoid valve, etc.).
Figure 27 Hot Gas Defrost with Electrical Drain Pan Heater Controller Wire Diagram