MK/MV – Medium Profile Series Unit Coolers (E206993_M)
60
Copyright 2018 KE2 Therm Solutions, Inc. . Washington, Missouri 63090
Q.1.61 November 2018
Page 7
• Check wiring to the EEV terminal on the KE2 Evap OEM board. Refer below for
proper wiring of the KE2-RSV EEV and other common EEV wiring.
M
OTOR
BLUE
ORANGE
YELLOW
RED
BLACK
M
OTOR
RED
GREEN
WHITE
BLACK
EEV
EMPTY
RSV
• The bare stranded wire of the EEV cable should be inserted so that the wire is di-
rectly touching the gate of the connector. If the gate is contacting the insulation of
the wire, it will not allow the controller to correctly operate the valve.
• If wires have been extended, check that colors have not been swapped
• Measure resistance across the EEV leads.
This will measure the resistance from
entire length of the lead wire, through the windings of the EEV and back to the
other lead. Remove the EEV leads from the terminals, and for KE2 RSV measure:
Check resistance across EEV leads:
Wire Colors
RSV-100 to 320 RSV-400 to 550
Blue - Orange
36 ohms
32 ohms
Blue – Yellow
36 ohms
32 ohms
Blue – Red
36 ohms 32 ohms
Blue – Black
36 ohms
32 ohms
Also check resistance between the windings:
Wire Colors
RSV-100 to 320 RSV-400 to 550
Orange – Yellow
96 ohms
65 ohms
Orange – Red
96 ohms
65 ohms
Orange – Black
96 ohms
65 ohms
Yellow – Red
96 ohms
65 ohms
Yellow – Black
96 ohms
65 ohms
Red – Black
96 ohms
65 ohms
For Sporlan SER-AA to L, measure:
Wire Colors
Black – White
100 ohms
Red – Green
100 ohms
Black – Green
Open
Red – White
Open
All values should be within 10% of stated values, otherwise indicating a wiring issue.
If absolutely sure of no wiring issue, the external coil may need to be replaced. For
valves with internal windings, the valve may need to be replaced.
• If electrical diagnosis reveals no issues, and no system issues are present, there
may be debris in the valve port. The valve can be driven open/closed several times
through the manual control, while also lightly tapping the valve in an attempt
to dislodge any debris. If valve has a strainer, strainer may need to be cleaned.
HSH / LSH Corrective Action -
Continued
Low Superheat Alarm Only
The Low Superheat Alarm is most commonly caused by the compressor failing to
start/ compressor not running. There is a common misconception in the industry
that the low pressure switch cut-in and cut-out pressure control on the condensing
unit is set correctly for the application from the factory.
The equipment manufacturers’ installation instructions recommend that the install-
ing contractor adjust the low pressure cut-in and cut-out to recommended settings
for the application. The low pressure cut-in and cut-out set point should be set to
either the ambient or space temperature, whichever is lower.
When the controller calls for refrigeration, if suction pressure is not able to rise to the
cut-in pressure before the EEV closes due to low superheat, the system will not start,
and a Low Superheat Alarm triggered.
Our technical support team typically sees an increase of these alarms in the fall when
the ambient temperatures begins to decrease. If the low superheat alarm is inter-
mittent, this is the most likely source of the alarm. Check the following:
• Low Pressure Control Pressure Switch.
Reduce the cut-out pressure to meet the
equipment manufacturer’s speci
fi
cation for the coldest ambient or box tempera-
ture, whichever is lower.
• Measure continuity across the low pressure control,
if it indicates a closed cir-
cuit, next check the compressor start components and continue diagnosis at the
condensing unit.
• Verify all fans are moving.
Check if there is a mechanical service switch for the
fans in the space being used inappropriately. If only one fan is not moving, verify
whether the fan is operational. Replace the motor if necessary.
• Check fan motor rotational direction and fan blade pitch
to ensure air is
fl
owing
in the proper direction.
• Check for diminished load due to low air movement across the coil.
This can
be caused by excessive frost build-up on the coil on the air entering and/or air exit-
ing sides of the coil. The fans should be turned o
ff
while checking for frost buildup
to allow a clear view of the coil. Product that is stacked too close to the coil and
impedes air
fl
ow through the coil can also be a source of diminished load.
• Check EEV and EEV wiring/cables
– Please see previous steps.
HSH / LSH Corrective Action -
Continued
KE2
Evap OEM
Alarm Troubleshooting Guide