WATER - (For Condensers)
Water-cooled condensers are designed to operate
with a water/propylene glycol solution, supplied at
a temperature of 41°F to 118°F (7.2°C to 10°C). A
minimum of 10 percent propylene glycol by weight
is recommended. If water piping is run outdoors,
35 percent propylene glycol by weight will give burst
protection, (not freeze protection), to approximately
–40°F (–40°C). Regardless of the amount of
propylene glycol, it must be ensured that the water
loop has adequate corrosion inhibitors.
The water flow requirements for each case are:
5-Door: 4 Gallons per Minute (GPM)
Auto balance valves are provided.
The inlet and outlet water connections are attached
using a 3/4 inch adapter. Use clamps (not supplied) to
tighten the hoses in place.
There are hand valves for system isolation located
on the inlet and outlet water connections. The hand
valves, hose adapter and their locations on the case are
shown on the illustrations on the next page. Trapped
air must be removed at high points of the water piping.
Balancing Valve
5-Door
Water =
R-290 (Propane) =
Balancing Valve
Water
Inlet
Water
Strainer
Water-cooled
condenser
Water-cooled
condenser
Water-cooled
condenser
Compressor
Compressor
Compressor
Capillary
Tube
Capillary
Tube
Capillary
Tube
Control Unit
Control Unit
Control Unit
Evaporator
Evaporator
Evaporator
5-Door
Water Flow Diagram