U-ONE
®
-SAFETY-LWL
Configuration manual
USL_KonfigManual-en_R3
25
5.1.1 Position-dependent current output
2 position values within the working area limits must be
entered to configure the position-dependent current output.
The smaller position value is assigned to current I
min
= 4
mA and the larger position value I
max
= 20 mA.
The following restriction applies:
Pos1 < Pos2
If the current position is outside of the set position range,
the current output is switched to a high impedance state
(I = 0 mA) (for default setting see section 6.7).
Alternatively, a setting can be selected that will output 4
mA or 20 mA if the set position range is not met or is
exceeded.
5.1.2 Speed-dependent current output
The speed n
20mA
must be entered to configure the speed-
dependent current output. A current of 4 mA will be flowing
when the module is at a standstill.
The following restriction applies:
n
20mA
< Mech. permitted speed.
If the speed range (n
current
> n
20mA
) is exceeded, the current
output is switched to high impedance (I = 0 mA) (for default
setting see section 6.7).
Alternatively, a setting can be selected that will output 20
mA if the set speed range is exceeded.
Fig. 5-1: position-dependent
current output
Fig. 5-2: speed-dependent
current output