Determining the calibration factor through calculation
Calibration factor = (rotations of the device shaft) x 8192 / real distance in system units.
Example:
34.5 m travel distance, corresponding to 125.7 rotations of the device shaft.
Calibration factor = 125.7 x 8192 / 34.5 = 29847.37
3.5.3 Determining the preset position
The preset position is a defined position point (calibration point).
Approach the calibration point (preset), turn off the drive and press the
button. The
current position is adopted as the calibration point.
Note
The calibration point must be between the upper and lower working area limits.
3.5.4 Completing the calibration process
1. values are saved in the USL by pressing
2. Press to complete the calibration. The system is calibrated
and can now be configured.