Hubbell Load:Logic Installation Instructions Manual Download Page 9

 
 
 
 
 
 

PD2794                                 02/2017 

                                                                                                                     Page 4 

Smart Switches 

 
These devices will automatically configure themselves to control the available loads within 5 seconds after being connected to 
the room controller.  For best results, do not press any buttons for 5 seconds after connecting a switch to the room controller. 
 
The buttons on the following switch catalog numbers are configured as toggle ON/OFF operation mode by default:  

RCS1x, 

RCS2x, RCS2x, RCS4x, and RCS6x

. These switches will self configure to sequentially control the loads.  For example, an 

RCS1x 

will control Load A and Load B simultaneously because it only has one button, an 

RCS2x 

will control loads A and B, 

independently because it has 2 buttons. 
 
The relationship between the buttons and the loads can be configured.  

See 

Manual Configuration

 below

.  

NOTE:

 If the zone 

has more loads than buttons, the last button in the sequence will automatically control the all remaining loads simultaneously. 
This insures that no load is left uncontrolled during the self-configuration process. 
 
Switches with specific functions like catalog numbers 

RCSNFx

 

and RCSTOx, RCSRLx, RCSSCx, RCSNRLFx 

will self-

configure by default to their respective descriptions.  For example; 

RCSRLx

 is a Raise/Lower dimmer.  Its default operation will 

be to change ALL the light levels of connected light fixtures.  The relationship between the switch functions and the loads being 
controlled can be modified.  

See 

Manual Configuration

 below. 

 
Daylight Sensor

 

 
The daylight sensor will self-configure to control Load A when connected to a room controller.  The photocell operation can be 
verified by observing Load A lighting while alternately covering the photocell (Load A light will be ON and bright if dimming 
enabled) or exposing the photocell to bright light (Load A light will be OFF or dimmed if so enabled). The relationship between 
the daylight sensor and the load(s) can be changed.  

See Manual Configuration below. 

 

Figure 4 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Manual Configuration

 

 
The process of manual configuration allows for the adjustment of certain functions by using the A and B pushbuttons and LED 
indicators on the room controller

’s enclosure.  The functions that can be adjusted are: 

 

1.  Assign loads to buttons and switches. 
2.  Configure loads for Manual ON (vacancy mode) or Auto ON operation mode. 
3.  Configure loads to respond to the photocell. 
4.  Calibrate the photocell. 

 

Summary of Contents for Load:Logic

Page 1: ...unit For Indoor use only Do not use outdoors Disconnect switch or a circuit breaker must be provided and marked as the disconnecting device The use of accessory equipment not recommended by the manuf...

Page 2: ...splayed These will include 1 Room Controllers Touch to display a list of room controllers found in the room Touch one of the room controllers to see a display showing controls for the relay s and dimm...

Page 3: ...ion after an outage Last State is the default setting Touch Set Level to enter a specific dim level for power up Use the Level slider to set the desired level or touch the box to use the keyboard to e...

Page 4: ...Groups A blue background fill in one of the 16 available groups indicates that this switch is selected to be a member of this group number A gray background fill indicates that the switch is NOT a me...

Page 5: ...ne of the 16 available groups indicates that this sensor is selected to be a member of this group number A gray background fill indicates that the sensor is NOT a member of the group By default the oc...

Page 6: ...urned OFF NOTE Make adjustments to the Design Level until the desired foot candle reading is achieved on the light meter at the task surface E Test Mode This is the factory default setting for Zone 1...

Page 7: ...rcuit s it controls The MAC address will be needed later during the system setup process 3 Turn power OFF at the service panel 4 Mount the room controller s enclosure to a knockout opening of an elect...

Page 8: ...Occupancy sensor with RP option 4 Loads NOTE Only one daylight sensor can be connected in each room zone Self Configuration The room controller s sequence of operation will automatically reconfigure...

Page 9: ...s RCSNFx and RCSTOx RCSRLx RCSSCx RCSNRLFx will self configure by default to their respective descriptions For example RCSRLx is a Raise Lower dimmer Its default operation will be to change ALL the li...

Page 10: ...2 Observe that the button is located slightly offset from the bezel opening The LED marked SVC will blink while the configuration button is being pressed 3 Release the configuration button and note t...

Page 11: ...Simultaneously press and hold buttons A and B for three seconds until LED A begins to blink rapidly This indicates the room controller has transitioned from load configuration mode into photocell con...

Page 12: ...n is complete the room controller will automatically exit configuration mode and return to normal operation Daylight harvesting will now be active based on the settings made during configuration Reset...

Reviews: