ON/OFF Mode

: All controlled lighting will turn OFF based on the settings.  The controlled lighting will be OFF as long 

as there is sufficient daylight to maintain the desired minimum task light level. 

 

Design Level

: The target minimum foot candle level at the task work surface. 

 

At Sensor

: Indicates the current amount of daylight visible to the daylight sensor.  Touch <

Get Level

> at any time 

to refresh the daylight level. 
 

At Task

: The amount of light in foot candles as read by a light meter placed at the task surface. Take this reading 

with the indoor lighting turned OFF. 
 

Dead Band (%)

: Provides a band between ON and OFF to prevent unwanted cycling of the load. Typically a 

setting of 5% works well. 

 

Make changes as needed. Touch the <

Accept

> button to save the changes or 

touch the <

Back

> button to exit WITHOUT saving the changes. 

 

C. 

Step Relay Mode

: High, low, OFF switching control based on the 

Primary/Secondary setting for the controlled relay(s) 

 

D. 

Full Dimming Mode

: Full range dimming in response to daylight. 

 

Design Level

: The target minimum foot candle level to be maintained at the 

work surface.  Enter the specified foot candle level. 

 

At Sensor

: Indicates the current amount of daylight visible to the daylight 

sensor.  Touch <

Get Level

> at any time to re read the daylight level. 

 

At Task

: The amount of light in foot candles as read by a light meter placed at the task surface.  Take this reading 

with the electric lighting turned OFF. 

 

NOTE

: Make adjustments to the Design Level until the desired foot candle reading is achieved on the light meter 

at the task surface. 

 

E. 

Test Mode

: This is the factory default setting for Zone 1.  Test mode causes the controlled lighting to react quickly to 

bright and dim light such as passing the beam of a flashlight across the daylight sensor. 

 

7. 

Preset Settings

: Touch to display the preset setup page.  Use the Preset Select pull down to choose which preset (1 - 16) this 

button will affect. 

Note

: the factory default programming, sets Preset 1 to 100%, Preset 2 to 75%, Preset 3 to 50%, and Preset 

4 to 25% for all dimmers. 

NOTE

: The “Include” setting determines if this preset will affect the associated dimmer or relay. If the 

box is not checked, this preset will NOT change this dimmer or relay when activated. 

 

Fade Time

: The fade time for transitions between presets can be set between 1 second and 18 hours. The factory default 

fade time is 5 seconds. Use the sliders or type in the box to change the fade time for this preset. 

 

Dimmers

: Use the slider or type in the box to set the desired dimmer level for each dimmer. 

 

Relays

: Use the controls to set if the relay will be turned ON or OFF when this preset is activated.  

 
After all settings have been selected, touch the <

Save

> button at the top of the screen.  A <

Test

> button is also provided at the top 

of the screen.  This button will activate the current preset exactly as if the preset button on the actual switch is touched. 
 

NOTE

: Touching the <

Test

> button immediately after saving a preset will have no affect since the lighting will already be set to the 

levels defined for the current preset. 

Summary of Contents for Load:Logic

Page 1: ...unit For Indoor use only Do not use outdoors Disconnect switch or a circuit breaker must be provided and marked as the disconnecting device The use of accessory equipment not recommended by the manuf...

Page 2: ...splayed These will include 1 Room Controllers Touch to display a list of room controllers found in the room Touch one of the room controllers to see a display showing controls for the relay s and dimm...

Page 3: ...ion after an outage Last State is the default setting Touch Set Level to enter a specific dim level for power up Use the Level slider to set the desired level or touch the box to use the keyboard to e...

Page 4: ...Groups A blue background fill in one of the 16 available groups indicates that this switch is selected to be a member of this group number A gray background fill indicates that the switch is NOT a me...

Page 5: ...ne of the 16 available groups indicates that this sensor is selected to be a member of this group number A gray background fill indicates that the sensor is NOT a member of the group By default the oc...

Page 6: ...urned OFF NOTE Make adjustments to the Design Level until the desired foot candle reading is achieved on the light meter at the task surface E Test Mode This is the factory default setting for Zone 1...

Page 7: ...rcuit s it controls The MAC address will be needed later during the system setup process 3 Turn power OFF at the service panel 4 Mount the room controller s enclosure to a knockout opening of an elect...

Page 8: ...Occupancy sensor with RP option 4 Loads NOTE Only one daylight sensor can be connected in each room zone Self Configuration The room controller s sequence of operation will automatically reconfigure...

Page 9: ...s RCSNFx and RCSTOx RCSRLx RCSSCx RCSNRLFx will self configure by default to their respective descriptions For example RCSRLx is a Raise Lower dimmer Its default operation will be to change ALL the li...

Page 10: ...2 Observe that the button is located slightly offset from the bezel opening The LED marked SVC will blink while the configuration button is being pressed 3 Release the configuration button and note t...

Page 11: ...Simultaneously press and hold buttons A and B for three seconds until LED A begins to blink rapidly This indicates the room controller has transitioned from load configuration mode into photocell con...

Page 12: ...n is complete the room controller will automatically exit configuration mode and return to normal operation Daylight harvesting will now be active based on the settings made during configuration Reset...

Reviews: