0HK.412.530SM
LW36A-126/145
High Voltage SF6 AC Circuit Breaker
15/30
Outline drawing of circuit breaker
Note: 1.base embedding, the M24 screw exserted length is 80mm
with 2 nuts, the base dimensions error is ±1mm.
2. the operating applied force: pull up=1800Kg, horizontal
force=2500Kg. total weight=1300Kg.
3. the circuit breaker earthed by 50×5 zinc coated, flat steel.
4. the dimension of 145KV circuit breaker marked in the ( ).
Drawing 9 groundwork installation