![Huayi LW36A-126 Operation Instruction Manual Download Page 5](http://html1.mh-extra.com/html/huayi/lw36a-126/lw36a-126_operation-instruction-manual_2179840005.webp)
0HK.412.530SM
LW36A-126/145
High Voltage SF6 AC Circuit Breaker
4/30
Continuous sheet 1
No.
Item
Unit
Parameter
19 On-off
time
ms
≤
60
20 Main
loop
resistance
µ
Ω
≤
40
21
Rated gas SF6 pressure (20
℃
meter’s
pressure)
0.6
22
Alarm/closedown pressure
(
20
℃
meter pressure)
MPa
0.55 / 0.50
23
Gas SF6 leak annual
%
≤
1
24
Moisture content of gas
ppm(v)
≤
150
25 Mechanical
life
次
6000
26
Wireless interfere level
µV
≤
500
Between fracture
3150/3625
27 Creepage
distance
To ground
mm
3150/3625
28
Gas SF6 weight of each circuit breaker
10
29
Circuit breaker weight
kg
1300
Main technical parameter of mechanism
sheet 2
No.
Item
Unit
Parameter
1
Auxiliary loop voltage
V
DC220
2
Rated operating voltage of
switch on coil and switch off coil
V
DC220
3
Rated operating current of switch
on coil and switch off coil
A
2
Rated voltage
V
AC220 /DC220
Voltage range of
normal operation
V
65%~110%
4
Energy
store
motor
Power
W
600
5
Energy store time of motor
s
≤
15
6
Manual energy store moment
N·m
≤
30
7
Loop voltage of heater and
lighting
V
AC 220
8
Rated voltage of auxiliary switch V
DC 220
9
Rated current of auxiliary switch
A
10
10 Connection point pairs of
auxiliary switch
20
2
.
2 Whole configuration feature of circuit breaker
The configuration shown as drawing 1, 3 poles porcelain vase install on a common base. The control
box lift on under the center of base, spring operating mechanism and control unit are installed in the