UPS5000-S-1600 kVA
User Manual
8 Technical Specifications
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
194
Item
Specifications
voltage is 2.25 V/cell.
End of discharge (EOD)
voltage
1.6–1.9 V/cell
Table 8-7
Output electrical specifications
Item
Specifications
System
Three-phase, four-wire, and PE
Voltage
380 V AC/400 V AC/415 V AC (line voltage)
Frequency
In normal mode, the frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50/60 Hz with a tolerance
of ±0.05%.
THDv
THDv ≤ 1% (full linear load)
THDv ≤ 3% (full non-linear load)
Power factor
1
Transfer time
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Output voltage imbalance
Voltage imbalance: ±3%; phase imbalance: ±2°
Overload capability
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60
minutes at a temperature lower than 40°C
110% < load ≤ 125%: transfer to bypass mode after 10
minutes (tolerance ± 0.1 min) at a temperature ranging
from 0°C to 30°C; transfer to bypass mode after 3 minutes
at a temperature ranging from 30°C to 40°C
125% < load ≤ 150%: transfer to bypass mode after 1
minute at a temperature lower than 30°C; transfer to bypass
mode after 30s at a temperature ranging from 30°C to 40°C
Load > 150% or a short circuit occurs: transfer to bypass
mode after 200 ms
Bypass overload capability:
100% load, 0–40°C ambient temperature: long-term
running
110% load, 0–30°C ambient temperature: long-term
running
125% load, 0–30°C ambient temperature: depends on
overtemperature protection after running for 10 minutes;
30–40°C ambient temperature: depends on
overtemperature protection