UPS5000-S-1600 kVA
User Manual
8 Technical Specifications
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
192
Item
Specifications
TUV
EN62040-1: 2013
CQC
CQC3108-2011
TLC
YD/T2165-2010
Electromagnetic
compatibility (EMC)
Conducted emission
EN/IEC62040-2
Radiated emission (RE)
EN/IEC62040-2
Low-frequency signal interference
IEC61000-2-2
Electrostatic discharge immunity
IEC61000-4-2
Conducted susceptibility
EN/IEC62040-2
EN/IEC61000-4-6
Radiated susceptibility
EN/IEC62040-2
EN/IEC61000-4-6
Electrical fast transient (EFT)
EN/IEC62040-2
IEC61000-4-4
Surge protection
EN/IEC62040-2
IEC61000-4-5
Power frequency magnetic field
IEC61000-4-8
Table 8-4
Mains input electrical specifications
Item
Specifications
System
Three-phase, four-wire, and PE
Rated voltage
380 V AC/400 V AC/415 V AC (line voltage)
Voltage range
80–280 V AC (phase voltage)
At 0–40°C: not derated when the voltage is 187–280 V AC;
derated to 35% load when the voltage is 187–80 V AC.
Rated frequency
50/60 Hz
Frequency range
40–70 Hz
Power factor
> 0.99 (full load)
> 0.98 (half load)
Harmonic current
THDi ≤ 3% (full linear load)
THDi ≤ 5% (full non-linear load)