4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
162
Whether the RCCMD SSL encrypted transmission is enabled on the WebUI of UPS5000
MDU and RCCMD client is irrelevant to the heartbeat detection function. Only when the SSL
encryption is enabled on the RCCMD client, the logs recorded by the RCCMD client are
marked with "(SSL...)".
On the RCCMD client, the IP address of the MDU that detects heartbeat needs to be added.
Then the UPS alive check function is supported; the RCCMD can check whether the UPS and
RCCMD communicate properly; the RCCMD can receive messages sent by the MDU.
Procedure
Step 1
On the RCCMD client, add the IP address of the MDU that detects heartbeat, as shown in
Figure 4-65.
Step 2
The UPS5000 MDU supports both ways of heartbeat detection. If the job configured for the
MDU event is set to
RCCMD TRAP
, the RCCMD client needs to be set to
by the use of
CS121/UPSMAN Traps
. If
by polling CS121/UPSMAN every x seconds...
is selected as
the method of detecting heartbeats, set the detection method. The default interval is 1800s and
detection is performed 100 times, as shown in Figure 4-65.
Figure 4-65
Heartbeat detecting mode on the RCCMD client
You can also manually detect heartbeat by clicking
Run alive check now...
.