5 Operations
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
167
After you set parameters on the
Settings Wizard
screen, choose
System Info
>
Settings
>
System
Setting
. Check that
System Capacity
,
Power module capacity
,
Requisite modules
, and
Redundant modules
match the actual values.
If dry contact signals are connected to the system, choose
System Info
>
Settings
>
Dry contacts
Set
and check that the connected dry contacts have been enabled and that the disconnected dry
contacts have been disabled.
If the system has connected to the remote EPO switch, you need to choose
Monitoring
>
Param.
Settings
>
System Settings
on the WebUI and check that
EPO detection
is set to
Enable
.
If the
Inconsistent parallel param.
alarm is generated, choose
System Info
>
Settings
, on the LCD
of the system and tap
Parameter Sync
.
Step 4
On the LCD of the system, view the system running status diagram to check that the UPS is
working in bypass mode.
----End
Offline Startup
The
Service Expert
app can be downloaded from Google Play and can run on Android.
For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.
Step 1
Open the
Service Expert
app on the mobile phone.
Step 2
On the home screen of the app, tap
Startup
to access the
Set Startup
screen.
Step 3
Set
Site
and
Device Type
as required, and tap
Offline Activation
.