UPS2000-G-3 kVA
User Manual (CTC)
5 Operations
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
48
Set
Voltage level
and
Frequency level
based on the rated voltage and frequency. In the
case of single-phase output, set
Voltage level
to 100 V (default), 110 V, or 120 V.
Battery parameters are configurable in non-battery mode or non-battery ECO mode.
Set
Battery capacity
to the total capacity of all batteries actually connected. The value
ranges from 100 Ah to 1000 Ah. The default value is 100 Ah.
The preset password is
000001
, used to enter the
Settings
menu.
The default feature code is
999999
, used to restore the preset password.
5.2.1 Starting the UPS in Normal Mode
Procedure
Step 1
Press and hold the MANUAL ON/OFF button on each lithium battery for at least 5s and less
than 15s to activate the lithium battery.
Step 2
Close the upstream AC input circuit breaker for the UPS based on site requirements.
The initialization screen is displayed.
Step 3
The UPS enters bypass mode. When the initialization is complete, perform the following
operations:
Initial startup
On the
Settings wizard
screen, set the language (the preset language is English), system
parameters, and battery parameters. Press
. The standby screen is displayed.
Figure 5-1
Settings wizard
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the standby
screen, press
to enter the main menu. Choose
Main Menu
>
Settings
>
System
Parameters
>
Output
to view output settings.
Step 4
Choose
Settings > Battery Parameters
, and set the
Input power limiting
based on the
actual situation.